期刊文献+

高压电缆温度在线监测系统中热点位置研究 被引量:3

Hotspot Location of Surface Temperature On-line Monitoring System for High Voltage Cable
下载PDF
导出
摘要 基于光纤的分布式温度测量系统是一种利用激光在光纤中的传播特性,实现实时测量空间温度场的技术。文章介绍了用于高压电缆表面温度测量的光纤测温系统,建立了高压电缆的热路模型,分析了不同位置表面温度对电缆线芯温度计算结果的影响,给出了不同排列方式下光纤安装位置的指导性意见。 The technology of distributed temperature sensing based on fiber is a new technique surveying the real-time distribution of spatial temperature pattern. This technology is based on the propagation characteristic of laser spreading in optical fiber. This paper introduced the distributed temperature sensing based on fiber which is used to monitor the surface temperature of high voltage cable, and gave out the thermal circuit model to calculate the temperature of cable core by surface temperature, and analyzed the effect on the calculation of cable core temperature by different hotspot on the cable surface, and gave out the guidance of the fiber position of different arrangement of cable.
作者 盖文福
出处 《电力设备》 2008年第9期50-52,共3页 Electrical Equipment
关键词 分布式温度测量系统 高压电缆 热点 光纤 distributed temperature sensing system high voltage cable hotspot fiber
  • 相关文献

参考文献5

二级参考文献21

  • 1李晓松,陈乔夫,胡贵,李荣华.超导变压器绕组环流研究[J].高电压技术,2005,31(8):1-3. 被引量:6
  • 2梁永春,孟凡凤,王正刚,李忠魁,李彦明.电缆群邻近效应的计算和优化排列[J].电工电能新技术,2006,25(2):39-41. 被引量:8
  • 3Mostafa. Ahangrani, Torsten Gogolla. Spontaneous raman scattering in optical fibers with modulated temperature raman remote sensing [J]. Journal of Lightwave Technology, 1999,17(8):1379-1391.
  • 4H o bel M, Richa J, Wtithrich M, et al. Highresolution distributed temperature sensing with the multiphoto-timing technique [J]. Applied Optics,1995,34(16):2955-2967.
  • 5Dakin J P, Pratt D J. Temperature distribution measurement using raman ratio thermometry[J].SPIE Fiber Optic and Laser Sensors, 1985,566:249-256.
  • 6深圳市麦普实业有限公司技术资料.光纤分布式温度监测系统在关键性动力电路中的应用[Z].,2002..
  • 7IEC Standard 1994-12 Calculation of the continuous current rating of cables (100% load factor)[S].Geneva,Switzerlang:International Electrotechnical Commission,1994.
  • 8George J Anders.Ration of electric power cables,ampacity computations for transmission,distribution,and industrial applications[M].New York:IEEE Press,1997.
  • 9Ferkal K,Poloujadoff M,Dorison E.Proximity effect and eddy current losses in insulated cables[J].IEEE Transactions on Power Delivery,1996(3):1171-1178.
  • 10Sergio,Berleze L M,Robert Rene.Skin and proximity effect in nonmagnetic conductors[J].IEEE Transaction on Education,2003,46(3):368-373.