摘要
利用有限元法计算了二维场中的电场强度,并分析了油纸复合绝缘引起的电场畸变。在最不利的情况下,油隙和纸角中的场强最大值Emax分别为均匀介质场强的2.0倍和1.7倍。研究结果对电力变压器绝缘结构设计和故障分析具有参考价值。
A finite-element method has been used to calculate the electric field strength in 2-dimensional field and to analyze the electric field distortion caused by oil-paper compound insulation structure in this paper. In the worst situation,the maximum of electric field strength(Emax) in oil gap and paper corner is 2.0 and 1.7 times respectively as much as those in even medium field,and the conclusion given in this paper can be used for reference in design for transformer insulation and inanalysis of insulation faults in power transformer.
出处
《变压器》
北大核心
1997年第11期5-9,共5页
Transformer
关键词
电力变压器
电介质
场强畸变
绝缘
Power transformer, Dielectric, Field strength distortion, Insulation