摘要
基于对上海医院的大规模调研,一般科室与关键科室不同的控制要求使得集中冷源难以节能运行,采用本文提出的双冷源专用新风机组可以不改变原有系统而保证关键科室的新风处理要求,从而实现"湿度优先控制",经济、有效地解决关键科室温湿度的控制,提高室内空气品质,有效地防止生物性污染。
According to the results of extensive investigation of existing hospitals in Shanghai, it was found that the conventional central cooling system didn't work well in the energy - saving mode because of the different humidity requirements of general departments and key departments. The FAU with dual cooling source can meet the handling requirement of the fresh air for key departments with the existing AC system unchanged to realize the "humidity - prior control" method and control the key department's temperature and humidity economically and effectively thereby improving the indoor air quality and preventing bio - contamination effectively.
出处
《制冷技术》
2008年第3期36-40,共5页
Chinese Journal of Refrigeration Technology
关键词
双冷源新风机
组机器露点
湿度优先控制
节能改造
FAU with dual - cooling source, apparatus dew point, humidity prior control, energy - saving reconstruction