750kV沿线避雷器限制操作过电压研究 被引量:9

Adopting line surge arresters to suppress switching overvoltages in 750 kV EHV transmission lines
原文传递
导出
摘要 以中国即将建设的兰州东-银川东750 kV输电线路工程为背景,结合国外对操作过电压水平的研究,利用电磁暂态计算程序(PSCAD/EMTDC)分别计算了沿线装设多组避雷器对三相合空线、单相自动重合闸操作过电压的限制效果。计算表明,如果不装设沿线避雷器,三相合空线、单相自动重合闸操作过电压最大值分别为2.45 p.u.和2.63p.u.,而采用沿线装设多组避雷器的方法可以将上述两种750 kV线路的操作过电压抑制到1.80 p.u.以下,甚至更低。另外,随着避雷器组数的增加,通过避雷器的总能量会有所增加,但单个避雷器的通流容量却有所下降。 Arresters were installed along a 750 kV high voltage transmission line to suppress switching overvoltage. The effects of the number and positions of arrestor on the 750 kV Lanzhoudong-Yinchuandong transmission line on the switching overvoltages, including three phases energizing line without load and single phase auto-reclosing, were analyzed using the electromagnetic transient program PSCAD/EMTDC. The results show that without any arresters, the maximum ovcrvoltage while three phase energizing line with no load is 2.45 p.u. and for single auto-reclosing is 2.63 p.u. With arresters, the two overvoltages are suppressed to 1.80 p.u. or less which show that the attesters effectivity suppress switch overvohages in extra-high voltage (EHV) line. Besides the overvohage amplitudes, the energy passing the arresters is also important. As the number of arresters increases, the total energy passing the arresters increases but the energy passing each arrester decreases.
出处 《清华大学学报(自然科学版)》 EI CAS CSCD 北大核心 2008年第10期1545-1548,共4页 Journal of Tsinghua University(Science and Technology)
关键词 750 KV输电线路 操作过电压 金属氧化物避雷器 通流容量 : 750 kV transmission line switching overvoltage metal oxide arrester (MOA) capacity of energy
  • 相关文献

参考文献7

二级参考文献50

共引文献265

同被引文献63

引证文献9

二级引证文献21

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部