摘要 介绍了两种新型无溶液泵和精馏装置的氨水吸收式制冷空调系统(无回热式和回热式)。首先对两系统的结构特点和循环过程进行了阐述,然后在不同发生器溶液存留倍数下对两系统进行了热力计算分析比较,然后对两系统进行了(火用)计算分析比较。经分析,在理想情况下无回热式系统的热力系数为0.249,总体(火用)效率为0.111;回热式系统的热力系数为0.454,总体效率为0.202。 Two different novel ammonia-water absorption refrigeration (AAR) air conditioning systems without solution pump and distillation equipment were presented, one with solution heat exchanger and the other without. The structure and circulation characteristics of the two systems were illustrate at first. Then the thermodynamic characteristics were calculated under different solution reservation of generator β. Exergy analysis was evaluated at last. The results show that the system with solution heat exchanger has higher thermodynamic and exgery coefficients but more complex compared with the system without it. Under ideal condition (β = 0), coefficient of performance of the system with solution heat exchanger was 0.454 , and the overall exergy coefficient was 0. 202, while those of the system without solution heat exchanger were 0. 249 and 0.111.
出处 《太阳能学报》 EI CAS CSCD 北大核心 2008年第10期1192-1196,共5页 Acta Energiae Solaris Sinica
基金 国家自然科学基金(5017603650276048)
关键词 新型 氨水 吸收式 制冷 热力分析 [火用]分析 novel absorption system ammonia-water refrigeration thermodynamic exergy
  • 相关文献

参考文献4

  • 1Ziegler F. Recent developments and future prospects of sorption heat pump systems[J]. Int J Therm Sci, 1999, 38 (3) : 191--208.
  • 2Misra R D, Sahoo P K, Gupta A. Thermoeconomic evaluation and optimization of a double effect H2O/LiBr vapour-absorption refrigeration system [ J ]. Int J Refrigeration, 2005, 28(4) : 331--343.
  • 3吴裕远,陈流芳,陈燕.无溶液泵三元溶液吸收式制冷与空调系统[P].中国,发明专利,200610042763.8,2006.
  • 4吴裕远,陈流芳,陈燕.回热型无泵三元溶液吸收式制冷与空调系统[P].中国,发明专利,200610042768.0,2006.

共引文献1

同被引文献11

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部