污水源热泵机组冬季运行工况实测与分析 被引量:7

Measurement and analysis of operating conditions of sewage source heat pump units in winter
下载PDF
导出
摘要 以采用城市原生污水为热泵冷热源的北京悦都大酒店的热泵机组为研究对象,测试了机组的污水进出口温度,蒸发器侧、冷凝器侧的进出口温度和压缩机的耗电量,根据测试数据考察了热泵机组在以城市污水为热源时的工作性能。测试期间机组运行稳定,冬季的平均制热性能系数COP为3.71,测试分析结果可供污水源热泵系统的设计和工程应用参考和借鉴。 Taking the urban sewage source heat pump units in Beijing Yuedu Hotel as study object, tests the inlet and outlet temperatures of the sewage, evaporator and condenser and the power consumption of the compressor. Based on the testing data, explores the operating performance of the heat pump units with urban sewage as heat source. During the testing period, the heat pump units operate steadily and the average coefficient of performance in heating conditions is 3.71. The results can be used for a reference in design and engineering application of sewage source heat pump systems.
机构地区 哈尔滨工业大学
出处 《暖通空调》 北大核心 2008年第11期133-136,共4页 Heating Ventilating & Air Conditioning
基金 国家自然科学基金资助项目(编号:50578048) 北京市"供热 供燃气 通风及空调工程"重点实验室开放课题(编号:KF200503)
关键词 污水源热泵机组 性能系数 耗电量 sewage source heat pump unit, coefficient of performance, power consumption
  • 相关文献

参考文献9

二级参考文献18

  • 1李晓明,崔福义,周红.污水源热泵的经济评价[J].煤气与热力,2005,25(4):52-55. 被引量:23
  • 2吴坤,张欢,赵海波.遗传算法在水—水热泵优化研究中的应用[J].暖通空调,2005,35(7):9-13. 被引量:8
  • 3吴荣华,张承虎,孙德兴.城市原生污水与其他冷热源的比较研究[J].暖通空调,2006,36(1):43-46. 被引量:20
  • 4龙惟定 丁文婷.住宅集中空调--21世纪的新消费热点.上海市制冷学会1999年学术年会论文集[M].,1999.615-619.
  • 5国家统计局.中国统计年鉴-2000[M].北京:中国统计出版社,2000..
  • 6上海市统计局.2000上海统计年鉴[M].北京:中国统计出版社,2000..
  • 7张蓓红.住宅建筑集中式空调系统的可行性研究:[硕士学位论文].上海:同济大学,1999..
  • 8-.上海高层建筑空调对能源和环境的影响研究报告.中国同济大学与日本早稻田大学合作研究项目[M].,2000..
  • 9马国远 彦启森.寒冷地区用空气源热泵的试验研究[A]..全国热泵和空调技术2001年交流会论文集[C].[s.l.]:[s.n.],2001.63-65.
  • 10马最良.哈尔滨寒冷地区传统供暖的新型双级耦合热泵供暖系统的介绍[A].哈尔滨:高寒地区电采暖实用技术研讨会论文集[C].2002.

共引文献117

同被引文献77

引证文献7

二级引证文献19

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部