摘要
采用Wilson法对14个表面式冷却器元件进行了管内紊流强制对流换热系数的测定。实验结果表明,实测值与用BoelterDitus公式计算值的偏差均在工程应用许可范围内,证实了在空冷器管组内流体紊流换热系数可按Doelter-Ditus公式计算。
Measured the turbulent flow and heat transfer coefficients for fourteen different air coolers using Wilson method. The tested heat tranfer coefficients agrees satisfactorily with those predicted by the Boelter Dittus formula. Concludes that the Boelter Dittus correlation is still valid for calculating the turbulent heat transfer coefficients in pipes of the air cooler.
出处
《暖通空调》
北大核心
1997年第A10期64-67,63,共5页
Heating Ventilating & Air Conditioning
基金
机械电子工业部基金
关键词
紊流转换
热阻分离法
冷却器
空调系统
turbulent heat transfer, heat resistance sparating method, air cooler