期刊文献+

严寒地区土壤源热泵系统的运行性能分析 被引量:17

Simulation Analysis on Operating Performance of GCHP in Severe Cold Area
原文传递
导出
摘要 本文针对沈阳市1栋典型办公建筑,首先采用TRNSYS软件建立了土壤源热泵系统与常规冷热源系统的模型,并进行了全年动态能耗模拟,通过模拟发现土壤源热泵系统在该地区的运行状态比较稳定。而后,将土壤源热泵系统与常规冷热源系统进行比较,从节能效益方面分析了土壤源热泵系统在该地区应用的可行性。 In this paper,taking a typical office building in Shenyang as an example,models of ground couple heat pump (GCHP) system and conventional system by the software of TRNSYS were established, and the annual dynamic energy consumption was simulated. It was observed that the operating situation was stable. Furthermore, GCHP system was compared with conventional system from the aspect of energy efficiency and the feasibility of applying GCHP system in this area was analyzed.
作者 钱程 徐伟
出处 《建筑科学》 北大核心 2008年第12期77-80,共4页 Building Science
关键词 土壤源热泵 严寒地区 动态模拟 节能 GCHP, severe cold area, dynamic simulation, energy efficiency
  • 相关文献

参考文献2

二级参考文献2

  • 1Parkerson W. Analysis of experimental ground coil data for heat pump design proceedings[ J]. Midwest Power Conference, 1951, (8)488 -493.
  • 2周漠仁.流体力学泵与风机(第三版)[M].北京:中国建筑工业出版社,1994..

共引文献34

同被引文献116

引证文献17

二级引证文献60

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部