Application of Voltage Response Method to Condition Assessment of Power Transformer 被引量:2

Application of Voltage Response Method to Condition Assessment of Power Transformer
下载PDF
导出
摘要 Power transformer is one of the most important equipment in the power system.Its operating condition affects the reliability of power supply directly.Therefore,in order to guarantee transformer operation safely and reliably,it is necessary to assess condition of power transformer accurately.Return voltage method based on voltage response measurements is still a new non-intrusive diagnosis method for internal insulation aging of transformer.In this paper the technique and application of return voltage measurement and some results of voltage response measurements of several transformers was introduced.Voltage response measurements were performed on various transformers with different voltage grades,various operating periods,different moisture contents and aging degrees on site.Derived moisture contents from return voltage measurement were compared with the corresponding moisture contents obtained from the analysis of oil samples.Based on on-site experiments and theoretical analysis,the criteria for insulation state of transformer are proposed.Moisture condition of transformer insulation can be determined by using return dominant time constant,and a good correlation between aging degree and the return voltage initial slopes of the aged transformers.Field test performed on several transformers,its interpretation of results are also presented,which proves that return voltage measurements can be used as a reliable tool for evaluating moisture content in transformer insulation. Power transformer is one of the most important equipment in the power system.Its operating condition affects the reliability of power supply directly.Therefore,in order to guarantee transformer operation safely and reliably,it is necessary to assess condition of power transformer accurately.Return voltage method based on voltage response measurements is still a new non-intrusive diagnosis method for internal insulation aging of transformer.In this paper the technique and application of return voltage measurement and some results of voltage response measurements of several transformers was introduced.Voltage response measurements were performed on various transformers with different voltage grades,various operating periods,different moisture contents and aging degrees on site.Derived moisture contents from return voltage measurement were compared with the corresponding moisture contents obtained from the analysis of oil samples.Based on on-site experiments and theoretical analysis,the criteria for insulation state of transformer are proposed.Moisture condition of transformer insulation can be determined by using return dominant time constant,and a good correlation between aging degree and the return voltage initial slopes of the aged transformers.Field test performed on several transformers,its interpretation of results are also presented,which proves that return voltage measurements can be used as a reliable tool for evaluating moisture content in transformer insulation.
出处 《高电压技术》 EI CAS CSCD 北大核心 2008年第12期2674-2680,共7页 High Voltage Engineering
基金 Project Supported by Science and Technology Fund of Fujian E-lectric Power Limited Company(NC2006044) Scientific Research Fund of Fujian Education Depart ment(JB06045)
关键词 电压响应方法 电力变压器 评估 RVM 起始斜率 故障诊断 voltage response insulation aging condition assess power transformer initial slope return voltage fault diagnosis power equipment moisture content RVM dielectric response
  • 相关文献

参考文献15

  • 1Gubanski S M, Boss P, Csepes G, et al. Dielectric Response methods for diagnostics of power transformers[J]. IEEE Electrical Insulation Magazine, 2003, 19(3): 12-18.
  • 2Saha T K. Review of modern diagnostic techniques for assessing insulation condition in aged transformers[J]. IEEE Trans on Dielect Elect Insul, 2003,10(5): 903-917.
  • 3Zaengl W S. Dielectric spectroscopy in time and frequency domain for power equipment: Ⅰ theoretical considerations[J]. IEEE Electrical Insulation Magazine, 200a, 19(5):5-19.
  • 4Leibfried T, Kachler A J, Zaengl W S, et al. Ageing and moisture analysis of power transformer insulation systems[C] // Proceedings of CIGRE Session 2002. Paris, France: CIGRE, 2002: 12-101.
  • 5Saha T K, Purkait P. Investigations of temperature effects on the dielectric response measurements of transformer oil-paper insulation system[J]. IEEE Transactions on Power Delivery, 2008, 23(1): 252-260.
  • 6Bognar A, Csepes G, Kalocsai L, et al. Spectrum of polarization phenomena of long time constant as a diagnostic method of oil-paper insulating system[C]// Proceedings of the 3rd Inter national Conference on Properties and Applications of Dielectric Materials. Tokyo, Japan: IEEE, 1991:723-726.
  • 7Urbani G M, Brooks R S. Using the recovery voltage method to evaluate aging in oil-paper insulation[C]// 1998 IEEE International Conference on Conduction and Breakdown in Solid Dielec tries. Vasteras, Sweden: IEEE, 1998:93 97.
  • 8Jonscher A K. Dielectric relaxation in solids[M]. London, UK: Chelsea Dielectric Press, 1983.
  • 9Haefely Trench A G Tettex Instruments Division. Instruction manual for automatic recovery voltage meter (RVM) type 5462 [M]. Basel, Switzerland: Haefely Trench A G Tettex Instruments Division, 2002.
  • 10Lu Y H, Tan C K, Phung B T, et al. Development of a computer-based data logger for return voltage measurements[C]// Proceedings of 2002 Australasian Universities Power Engineer ing Conference: Part 4 (High Voltage, Condition Monitoring). Melbourne, Australia; Australasian Committee for Power Engineering, 2002.

同被引文献21

引证文献2

二级引证文献30

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部