摘要
本文针对GIS变电站电压互感器误差试验的特点及面临的问题,详细分析了GIS电压互感器误差试验原理,并将变频技术应用于GIS电压互感器误差试验中。在实验室由标准电容和可调电感组成的串联回路,利用变频技术测量串联回路的谐振频率,通过计算对可调电感进行标定。在GIS变电站电压互感器测试时,利用变频技术测得GIS管道电容量,从而可计算得出工频谐振条件下应匹配的可调电感值。条件已标定的可调电感,通过工频谐振很容易获得误差试验所需的一次电压,能较好的解决GIS电压互感器误差试验面临的难题。
The puzzles and features of VT error test in electric substation of gas insulation system are studied, and the theories of VT error calibration test in GIS system are also analized in the essay. Converter technique is applied to the VT test in GIS system. Through building series resonant circuit by standing capacity and inductor in laboratory, and measuring the resonant frequency, we can calibrate the value of the variable inductor. In field test, the piping capacity is calculated by converter technique first, and then the variable inductor value under power resonance can be calculated. By adjusting the variable inductor, the primary voltage can be easily got through power resonance. Tests show that the method is objective and effective.
出处
《电测与仪表》
北大核心
2009年第1期6-8,共3页
Electrical Measurement & Instrumentation
关键词
变频技术
GIS变电站
标准电容
可调电感
电压互感器
误差试验
converter technique, electric substation of gas insulation system, standard capacitor, variable inductor, voltage transformer, error test