期刊文献+

PLC软冗余系统性能分析 被引量:17

Performance analysis of PLC software redundancy system
下载PDF
导出
摘要 研究了西门子可编程控制器(PLC)软冗余系统的软硬件组成及实现原理。典型的PLC软冗余系统由主/备的CPU、电源、I/O模块和总线等组成。一旦发生故障,备CPU接替主CPU工作,保证系统正常运行。分析了PLC软冗余系统在主CPU、电源、I/O模块和Profibus总线等分别发生故障情况下,不同故障发生时刻引发的软件中断和主备切换过程,得出了相应的主/备切换时间极限值的估算公式。分析了PLC软冗余系统的数据同步过程,得出了数据同步时间的估算公式。通过分析可知,PLC软冗余系统的主备切换时间和数据同步时间较长,适合于对实时性要求不严格的生产过程控制。 The structure of SIMATIC PLC software redundancy system and its implementation principle are studied. Typical PLC software redundancy system consists of master-backup CPU, power supply, I/ O module and field-bus. When breakdown occurs, the backup CPU runs instead of former master CPU to assure the normal operation. The changeover procedure is analyzed for different component breakdowns at different moments to get the estimation formula of corresponding maximum changeover time, and the data synchronization procedure is analyzed too to get the estimation formula of data synchronization time. Analytical results show that, the changeover time and data synchronization time of PLC software redundancy system are longer, suitable for the process control without strict requirement for real time performance.
出处 《电力自动化设备》 EI CSCD 北大核心 2009年第2期98-101,共4页 Electric Power Automation Equipment
基金 西安市工业科技攻关计划项目(GG200334)~~
关键词 软冗余 主备切换 数据同步 可编程控制器 网络故障 software redundancy master-backup changeover data synchronization PLC fault of network
  • 相关文献

参考文献12

二级参考文献14

  • 1郑伟民 汤志忠.计算机系统结构(第二版) [M].北京:清华大学出版社,1998..
  • 2Manfred Popp 杨昌琨译.PROFIBUS—DP快速入门[M].中国机电一体化技术应用协会,1997..
  • 3SIEMENS. Software Redundancy for SIMATIC S7- 300 and S7 -400.1999.
  • 4邱公伟,实时控制与智能仪表多微机系统的通信技术,1996年,314页
  • 5浙江大学自动化中心.可编程序控制器系统[M].浙江大学出版社,2000..
  • 6SIEMENS.STEP 75.3编程手册.
  • 7SIEMENS.STEP7 5.3梯形图手册.
  • 8SIEMENS.WINCC组态手册(1-6).
  • 9SIEMENS.S7—300硬件安装及模板规范手册.
  • 10唐济扬.用于自动控制系统的工业[J].通讯网络,2000,1.

共引文献101

同被引文献75

引证文献17

二级引证文献30

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部