期刊文献+

新型矿井低压电网选择性漏电保护装置研究 被引量:12

A New Mine Selective Earth Leakage Protection Device of low-voltage Distribution Networks
下载PDF
导出
摘要 在分析目前矿井低压电网漏电保护系统的基础上,提出了一种以数字信号处理器(DSP)为核心,基于附加直流电源检测和零序功率方向的新型选择性漏电保护方案,简化了传统漏电保护的设计,可以改善井下低压电网漏电保护的动作性能。重点分析漏电保护系统原理,简要介绍保护装置的实现。现场运行表明,系统实现了漏电保护的快速性、选择性和准确性。 A scheme of new style selective leakage protection is put forward, on the analysis of the existing leakage protection system for low-voltage distribution networks underground mine, based on the DC power supply additional testing and the zero-sequence power direction with digital signal processor (DSP) as the core, which simplifies the design of conventional leakage protection device and enhance levels of safety for low-voltage distribution networks underground. The principles of protective systems is analyzed emphatically, the realization of protection is introduced briefly. The operation in the field shows that the system achieves rapidity, selectivity and accuracy.
出处 《煤矿机电》 2009年第1期27-29,34,共4页 Colliery Mechanical & Electrical Technology
关键词 选择性 漏电保护 矿井低压电网 数字信号处理器(DSP) selectivity leakage protection mine low-voltage distribution networks digital signal processor (DSP)
  • 相关文献

参考文献3

  • 1高彦,王彦文,司书巍,等.选煤厂660V高阻接地系统选择性漏电保护装置的研究[C].2006中国国际供电会议论文集,2006.
  • 2申志远,刘卫国.工矿企业供电[M].徐州:中国矿业大学出版社,1995.
  • 3胡天禄.漏电保护参数与安全的关系[J].中国矿业大学学报,1991,(4).