期刊文献+

回热器对R404A制冷系统性能影响的实验研究 被引量:5

Experimental study on influence of liquid-suction heat exchanger on the performances of R404A refrigerating system
下载PDF
导出
摘要 进行了回热器对R404A制冷剂性能影响的实验研究,得出了有无回热器工况下运行时机组的性能参数,并对它们进行了比较和分析。得到的结论是:回热器对R404A制冷系统性能在低温工况下是有利的;回热器虽然会使制冷系统的制冷量和COP增加,但都会引起压缩机排气温度升高,某些工况最高排气温度达到了162.8℃,会影响压缩机的正常运行。 An experimental study on the influence of liquid - suction heat exchanger on the performances of R404A refrigerant was carried out. Performance parameters of R404A refrigerating system with liquid - suction heat exchanger and without liquid - suction heat exchanger were tested. They were compared and analyzed. The experimental study led to result as follow: it is beneficial to use liquid - suction heat exchanger in R404A refrigerating system under low temperature conditions ; liquid - suction heat exchanger improves the cooling capacity and COP, increases the discharging temperature greatly, with the highest dischar- ging temperature of 162.8℃, which mig19t influence the normal operation of compressor.
出处 《低温与超导》 CAS CSCD 北大核心 2009年第2期60-64,共5页 Cryogenics and Superconductivity
关键词 R404 回热器 试验研究 R404A, Liquid- suction heat exchanger, Experimental research
  • 相关文献

参考文献5

  • 1Domanski P A, Didion D A. Thermodynamic evaluation of R22 alternative refrigerants and refrigerant mixtures [ J ] ASHRAE Transactions, 1993,99 (2) : 636 - 48.
  • 2Domanski P A, Didion D A, Doyle J P. Evaluation of suction - line / liquid - line heat exchange in the refrigeration cycle[J]. Rev. Int. Froid. , 1994,7(7) :487 -93.
  • 3Klein S A,Reindl D T, Brownell K. Refrigeration system performance using liquid - suction heat exchangers [ J ]. Intemation Journal of Refrigeration, 2000,23:588 - 596.
  • 4向立平,曹小林,席占利,欧阳琴.回热器对制冷循环性能影响的研究[J].制冷与空调(四川),2005,19(4):38-42. 被引量:19
  • 5张永钢 吴宣中.基于R404A的小型冷风机的实验研究.制冷学报,2002,.

二级参考文献2

共引文献18

同被引文献21

引证文献5

二级引证文献7