期刊文献+

并联补偿电容对限流器运行影响的仿真研究 被引量:6

Simulation research on the effect of the paralleled compensating capacitor on the solid state fault current limiter operation
下载PDF
导出
摘要 当发生短路故障时,限流器通过插入等效限流电抗来限制短路电流。此等效限流电抗主要是感性的,因此与系统中的容性负载作用可能发生谐振,产生不利影响。对感性负荷带并联补偿电容的情况下,新型桥式固态限流器(不带旁路电感和带旁路电感)采用预触发与不采用预触发时的运行工况及是否会产生谐振进行了理论分析与比较,并通过系统仿真对分析结果进行了验证。 The fault current limiter inserts the impedance to limit the fault current when the fault happens. Since the limiting impedance is inductive, it may bring the resonance with capacitive load and does harm to power system. In the paper, in the situation of paralleling a compensating capacitor with the inductive load, the operation and resonance situation is compared and analyzed theoretically when the new bridge type solid-state fault current limiter (both with paralleled inductance and not) is pre-triggered or not. It is proved to be valid through system simulation.
作者 金鑫 江道灼
出处 《电力系统保护与控制》 EI CSCD 北大核心 2009年第4期54-57,61,共5页 Power System Protection and Control
关键词 电力系统 短路故障 新型桥式固态限流器 并联补偿电容 谐振 power system short circuit bridge type solid-state fault current limiter paralleled compensating capacitor resonance
  • 相关文献

参考文献10

二级参考文献85

共引文献201

同被引文献46

引证文献6

二级引证文献41

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部