期刊文献+

一起国产12kV KYN手车式开关设备爆炸的分析与对策

Analysis and Countermeasure on KYN Type 12kV Switchgear's Explosion
下载PDF
导出
摘要 通过对一起国产12kVKYN手车式开关设备在冷备用状态下发生爆炸烧毁的故障原因分析和总结,指出目前运行的许多国产12kVKYN手车式母线提升柜存在结构性弱点,容易在天气骤变过程中出现凝露,发生绝缘闪络故障,并提出了改进建议。 By analysis and summary on an explosion of Chinese KYN type 12kV switchgear in cold standby condition, it points out, there are structural weaknesses in bus lifting cubicle of that type switchgear, especially, condensate dew is appeared when weather changes suddenly, and the insulation flashover fault should be happened. Countermeasures and suggestions are put forward. To control insulation that type switchgear modification should be regarded for manufacturer and end user.
作者 巫环科
出处 《广东输电与变电技术》 2009年第2期23-25,共3页 Guangdong Power Transmission Technology
关键词 母线提升柜 凝露闪络 故障分析 Bus lifting cubicle Flashover by condensate dew Failure analysis