摘要 通常在发变电站铺设一层厚度为5-20cm砾石或沥青混凝土路面,该层路面对人脚对大地的接地电阴Rf有较大影响。本文基于双层土壤模型,提出了Rf的精确计算方法,并给出了准确度很高的简化计算公式,可供工程实际应用。 There is a gravel Layer in substation yards . The ground resistance of the foot R f is affected by the limited depth of the gravel layer. This paper presents a accurate method to calculate R f based on two - layer soil model. A simple empirical equation for determining the value of Rf is also presented and can be used for practical dessign propose.
作者 鲁志伟
机构地区 东北电力学院
出处 《电工技术学报》 EI CSCD 北大核心 1998年第2期62-64,共3页 Transactions of China Electrotechnical Society
关键词 接地电阻 计算 电阻 变电站 发电站 : Footing Resistance Grounding Safety
  • 相关文献

参考文献2

  • 1解广润,电力系统接地技术,1991年
  • 2解广润,高压静电场,1962年

同被引文献5

  • 1EEE Guidefor safetyinAC SubstationGrounding,ANSI/IEEE Std.80—1986,1986.
  • 2B.Thapar,V.Gerez,H.Kejrlwal.Reduction Factor for the ground resistance of the foot in substation yards.IEEE Transactions Power Delivery,Vol.9,NO.1,pp.360—368,January l994.
  • 3H.R.Seedher,R.Kumar.A new expression for foot resistance in switchyards,in Proc.VIII Nat Power System.Cod,New Delhi,India,Dec.14—17,1994,PP,711—715.
  • 4EEE Guidefor safety in AC Substation Grounding,ANSI/IEEE Std.80—2000,2000.
  • 5张波,白永胜,杨杰,李琳,崔翔.对补偿法测2层土壤中接地网接地电阻的修正[J].高电压技术,2001,27(3):31-33. 被引量:8