摘要
介绍了双母线双分段接线方式下母差保护的配置,着重分析母线故障情况下母联开关或分段开关失灵以及发生死区故障母差保护的动作过程,阐明了母联开关失灵和死区故障与分段开关失灵和死区故障母差保护动作行为上的区别,列表说明发生这些故障时母差保护面板上信号灯动作情况。
This paper introduces the configuration of bus protection in dual-bus dual-subsection connection, and puts emphasis on analysis of action of bus differential protection in bus coupling breakers or sectional switches malfunction and dead-zone fault, and also expounds the differences between bus coupling breaker malfunction and sectional switch malfunction. The actions of the signal lamp in the platform of bus differential protection are listed when the faults happen.
出处
《江苏电机工程》
2009年第2期16-19,共4页
Jiangsu Electrical Engineering
关键词
开关失灵
死区故障
动作行为
分析
switch malfunction
dead-zone fault
action
analysis