期刊文献+

晶闸管触发脉冲形式对直流电弧炉工作电流设计的影响

Effect of the Thyristor Gate Triggering Pulse Type on the Design of DC EAFs Working Current
原文传递
导出
摘要 直流电弧炉用整流变压器漏抗值设计较一般电力变压器大,整流器换相时间延长。当工作电流设计不合理时,易使三相桥式相控整流器工作在非正常换相状态,即出现换相重叠和换相延迟现象。若采用不同形式的晶闸管门极触发脉冲,将导致不同的整流波形。因此,直流电弧炉工作电流设计应尽量避免进入该区域。 Because leakage inductances value of rectiformer used in DC EAF is larger than common power transformer,rectifier has longer commutation time.When the design of working current is irrational,three-phase bridge phase control rectifier is easy to work in an innormal commutation state,in other words,to appear the phenomena of commutation overlap and commutation delay.If we apply different triggering pulse in type to the gate terminal of thyristor,we shall get different rectification wave.Thus,it must be avoided to design the working current of DC EAF into this region.
作者 雷惠 庄斌星
出处 《冶金设备》 1998年第1期5-8,共4页 Metallurgical Equipment
关键词 直流电弧炉 晶闸管 电炉炼钢 工作电流 DC EAF Thyristor Three-phase bridge phase control rectification Commutation