轧后库厂房结露情况实测分析

MEASUREMENT AND ANALYSIS OF DEWFALL OF ONE AFTER COLD ROLLING STOREHOUSE'S MILL BUILDING
原文传递
导出
摘要 某冷轧钢轧后库为全钢结构厂房,厂房屋面板下表面常有结露现象发生。通过对该厂房室内外温湿度的测量,定量分析了厂房结露的发生情况,对每月结露发生的概率和结露发生的时间进行分析和统计。实测数据表明在正常的生产条件下,在室外温度较低的月份厂房结露情况较为严重。室内相对湿度与室外相对湿度的相关性较大,室内外相对湿度的变化趋势是一致的。在室外温度相近的月份,室外相对湿度越大,厂房结露发生率越高。结露发生时间多集中在夜晚到凌晨,午后发生结露的概率较低。最后对厂房屋面结露的原因进行了总结,认为生产工艺有一定的热量和湿蒸汽散入室内,厂房通风条件较差,不利的室外温湿度环境和厂房围护结构不设保温是厂房结露现象发生的原因。 The after cold rolling storehouse is a steel workshop.There is dewfall phenomenon on the inner surface of the roof.The dewfall of the workshop is analysed by the means of measurement in this article.It is done the analysis and the statistics of the probability of dewfall in each month,and the dewfall time.Measured data indicate that dewfall under normal production conditions is more serious in the month when the outdoor temperature is lower.Indoor relative humidity and outdoor relative humidity associated with each other,and the trends of indoor and outdoor relative humidity are consistent.In the month of similar outdoor temperature,the greater the outdoor relative humidity is,the higher the incidence of the dewfall.The dewfall time is more concentrated at night to the dawn, while the dewfall probability is relative lower in the afternoon.Lastly,the article summarized the reasons of the dewfall,which include that a certain degree of heat and wet steam is scattered into the interior,the workshop's ventilation condition is poor,the outdoor temperature and humidity environment is unfavorable,and the workshop envelope is without insulation.
出处 《工业建筑》 CSCD 北大核心 2010年第S1期55-57,50,共4页 Industrial Construction
关键词 厂房 结露 实测分析 workshop dewfall measurement and analysis
  • 相关文献

参考文献4

二级参考文献22

  • 1王颖,施能,顾骏强,封国林,张立波.中国雨日的气候变化[J].大气科学,2006,30(1):162-170. 被引量:181
  • 2孟庆林,张玉,张磊.热气候风洞内测定种植屋面当量热阻[J].暖通空调,2006,36(10):111-113. 被引量:21
  • 3邵建涛,刘京,赵加宁,付志鹏,张文武.建筑外表面对流换热实验研究进展[J].建筑科学,2007,23(8):92-97. 被引量:6
  • 4章熙民 任泽沛 梅飞鸣 等.传热学[M].北京:中国建筑工业出版社,1985..
  • 5Clear R D, Gartland L, Winkelmann F C. An empirical correlation for the outside convective air-film coefficient for horizontal roofs [ J ]. Energy and Buildings, 2003,35 : 797-811.
  • 6Aya Hagishima, Jun Tanimoto. Field measurements for estimating the convective heat transfer coefficient at building surfaces [ J ]. Building and Environment ,2003,38 : 873- 881.
  • 7Barlow Janet F, Stephen E Belcher. A wind tunnel model for quantifying fluxes in the urban boundary layer [ J ]. Boundary-Layer Meteorology ,2002,104 : 131-150.
  • 8Ken-ichi Narita. Experimental study of the transfer velocity for urban surface with a water evaporation method [ J ]. Boundary-Layer Meteorology ,2007,122:293-320.
  • 9Goldstein R J, Cho H H. A review of mass transfer measurements using naphthalene sublimation [ J]. J Experimental Thermal and Fluid Science, 1995,10:416-434.
  • 10Ambrose D, Lawrenson I J, Sparke C H S. The vapor pressure of naphthalene [ J ]. J Chem Thermo dynam, 1975,7:1 173-1 176.

共引文献36

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部