摘要
通过对补偿电网"虚幻接地"、断线故障和单相接地故障3种运行方式的分析和比较,提出了以等值阻抗和系统不对称电压来识别这3种运行方式,并给出判断依据和基于晶闸管投切电容式消弧线圈的补偿电网运行方式的识别方案。
By analyzing and comparing three operational modes of compensated power network, i. e. virtual grounding, break-up-line fault and single-phase earth fault, the use of equivalent impedance and asymmetric system voltage is suggested for identifying the three modes. The identifying criterion is brought forward, and a scheme for identifying the operational modes of compensated power network is put forward based on the arc-extinction coil with thyristor series capacitor (TSC).
出处
《广东电力》
2009年第3期19-22,共4页
Guangdong Electric Power
关键词
补偿电网
断线故障
晶闸管投切电容式消弧线圈
compensated power network
break-up-line fault
arc-extinction coil with thyristor series capacitor (TSC)