摘要
通过动态试验将化学处理与物理方法结合起来,为工业循环冷却水的处理探索了一条新的途径——臭氧与磁化联合处理法。试验结果表明,经联合处理后,系统的阻垢率达70.80%,缓蚀率为50.13%,比单独处理时效果更好,二者可以发挥协同作用。
Chemical treatment and physical methods are combined in the dynamic test in which a new way is explored for treatment of recycling cooling water, that is combined application of ozone and magnetization. The best results show that: the antiscale rate of the system is 70. 80%, the anticor-rosion rate is 50. 13%, the effectiveness is better than that of single treatment, the two methods can give full play to coordinated action.
出处
《天津职业大学学报》
1999年第1期33-35,共3页
Journal of Tianjin Vocational Institute