摘要 计算了葛上±500kV直流输电工程上海直流接地极的溢流分布,指出了在引流电缆和馈电钢棒连接处溢流的过分集中是导致原上海直流接地极烧毁故障的主要原因之一。为此,合理选择引流钢棒的布置是延长上海直流接地极运行寿命的有效方法。 In this paper the current distribution of original and present Shanghai DC ground electrodes are calculated. It is pointed out that current over accumulation at the connected positions between feeder cables and electrode steel rods was one of the main reasons that cause original Shanghai DC
出处 《高电压技术》 EI CAS CSCD 北大核心 1998年第1期76-78,共3页 High Voltage Engineering
关键词 直流接地极 引流线 过电压保护 直流输电 DC ground electrode current distribution rational arrangement of feeder line
  • 相关文献

参考文献2

  • 1直流输电接地极研究报告之一,直流输电接地极腐蚀机理研究及上海直流接地极故障原因分析.华东电力试验研究院.1993.
  • 2Gezhouba-Shanghai HVDC Transmissission system:Feasiollity of ground electrods at Shanghai and Gezbouba for extended monopolar opeation,Teshmont Consultants Inc.July S1.1984.