分析了线端调压全绝缘有载调压变压器的冲击分布,提出把高压绕组中部断开,调压绕组接在高压绕组中部,可以有效改善冲击性能,减小变压器主绝缘距离。
The distribution of impulse for terminal voltage-regulating transformer with uniform insulation and OLTC is analysed in this paper. A way of voltage-regulating in middle-section of HV winding is presented to improve the properties to withstand lightning impulse effectively and to decrease the distance of main insulation between windings of transformer.
出处
《变压器》
EI
北大核心
1998年第2期17-20,共4页
Transformer
关键词
变压器
有载调压
绝缘
冲击
性能
可调压变压器
Transformer, On-load voltage-regulating, Insulation, Impulse, Property