The length of the trajectory is proposed as a function for the employment of the sensitivity analysis method in power system transient stability analysis. Its sensitivity to the faultclearing time is about 10 times higher than that of the energy function or the distance function. The integrating time is reduced to less than 3 s while the accuracy is maintained. It can also be used to provide parameter limits. Simulations on the WSCC 4 machine system and the New England system verify the effectiveness of sensitivity of trajectory length in transient stability analysis.
The length of the trajectory is proposed as a function for the employment of the sensitivity analysis method in power system transient stability analysis. Its sensitivity to the faultclearing time is about 10 times higher than that of the energy function or the distance function. The integrating time is reduced to less than 3 s while the accuracy is maintained. It can also be used to provide parameter limits. Simulations on the WSCC 4 machine system and the New England system verify the effectiveness of sensitivity of trajectory length in transient stability analysis.