翅片管换热器过冷管设计对系统性能影响研究 被引量:5

Investigation on the Subcooled U Tube Design of a Fin-tube Heat Exchanger on the Performance of the Air Conditioner
下载PDF
导出
摘要 试验对比研究在翅片管换热器底部设置1根U形管过冷、2根并联U形管过冷、2根串联U形管过冷的过冷效果,测试数据表明用2根U形管串联进行过冷的效果最好。当把2根铜管串联用于过冷时,对R22制冷剂在B工况测试条件下,与没有过冷相比,过冷度增加了1.1℃,能效比高出0.33W/W,提高了8.25%;对R410A制冷剂在B工况测试条件下,与没有过冷相比,过冷度增加了2.0℃,能效比高出0.10W/W,提高了2.69%。 Three kinds of subcooled U tube design of a fin- tube heat exchanger on the performance of the air conditioner were investigated experimentally. The 1 U tube, 2 parallel U tubes and 2 series U tubes at the bottom of a fin - tube heat exchanger were designed and tested. It is showed that the design of 2 series U tubes design will get the best performance of the air conditioner. Comparing to the no subcooled U tube design, the 2 series U tubes subcooled design gets the results of subeooling increasing 1.1 ℃, energy efficiency ratio increasing 0.33W/W, that is 8.25 percent for R22 refrigerant under B test of ARI 210- 240; and the subcooling increasing 2.0℃, energy efficiency ratio increasing 0.10W/W, that is 2.69 percent for R410A refrigerant under B test of ARI 210- 240.
出处 《制冷》 2009年第1期36-40,共5页 Refrigeration
关键词 翅片管换热器 过冷段 性能系数 试验研究 Fin- tube heat exchanger, Subcooled U tube, Energy efficiency ratio, Experimental investigation
  • 相关文献

参考文献3

二级参考文献29

共引文献39

同被引文献21

  • 1肖跃进,王岸林.铜铝冶金复合管应用于空调换热器研究[J].家电科技,2007(12):66-68. 被引量:5
  • 2唐亚林.室外换热器流路对变频空调APF的影响[J].家电科技,2014(6):60-61. 被引量:5
  • 3姜盈霓,虎小红.流程布置对翅片管换热器换热性能影响的研究现状与展望[J].制冷与空调,2007,7(3):14-20. 被引量:19
  • 4徐志亮,严玉雄.焓差法试验室调试常见问题分析[J].制冷与空调,2007,7(3):66-70. 被引量:9
  • 5蔡增基,龙天渝.流体力学泵与风机[M].北京:中国建筑工业出版社,2005.
  • 6LIANG S Y,WONGT N,NATHAN G K.Numerical and experimental studies of refrigerant circuitry of evaporator coils[J].International Journal of Refrigerant,2001,24(8):823-833.
  • 7LIANG S Y,WONG T N,NATHAN G K.Study on refrigerant circuitry of condenser coils with exergy destruction analysis[J].Applied Thermal Engineering,2000,20(6):559-577.
  • 8DOMANSKI P A,YASHAR D,KIM M S.Performance of a finned-tube evaporator optimized for different refrigerants and its effect on system efficiency[J].International Journal of Refrigerant,2005.28(6):820-827.
  • 9DOMANSKI P A.Simulation models for finned-tube evaporator and condenser-EVAP-COND 21[CP/DK].Gaithersburg,USA:National Institute of Standards and Technology.[2006-08-12].http://www2.bfrl.nist.gov/softuare/evdp-cond.
  • 10DOMANSKI P A.Simulation of an evaporator with non-uniform one-dimensional air distribution[J].ASHRAE Transaction,1991,97(1):793-802.

引证文献5

二级引证文献17

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部