高压直流换流站换流系统宽频建模研究 被引量:28

Wide-band Modeling of Converter Systems in HVDC Converter Stations
下载PDF
导出
摘要 高压直流(high voltage DC,HVDC)换流站电磁骚扰主要由阀体内的晶闸管在周期性的导通和关断过程中产生。该骚扰中的高频分量通过辐射和传导2种形式可能会对换流站内的通讯设备、保护与控制系统和载波系统以及换流站附近的无线电台站等产生影响,所以,建立换流系统的宽频等效电路模型对该骚扰进行计算和预测,研究其时频特性是进行干扰机理分析的前提条件。该文给出了HVDC换流站各主要设备的建模方法及其等效电路,包括阀组件、换流变压器、平波电抗器、滤波器等。其中,阀组件内各元件的阻抗通过网络分析仪测量,然后通过矢量匹配进行零极点提取,最后通过布隆法进行网络综合得到阀组件各器件的宽频等效电路。应用有限元方法计算了阀塔以及散热片的寄生电容参数。以阀塔作为整体,基于PSCAD/EMTDC建立了HVDC换流站换流系统宽频仿真模型。在此基础上,研究了传导电磁骚扰特性。计算结果和测量结果的比较,验证了该文建模方法的正确性。 Electromagnetic disturbance (EMD) is mainly caused by the periodic valve switching in HVDC converter station. This disturbance can cause high frequency conducted and radiative interference to the adjacent communication, computer equipment, carrier system and radio stations. So a wide-band model of converter system is necessary to predict the characteristic of the EMD source. Methods of modeling and the equivalent circuits of the main equipment in HVDC converter stations are presented, including valve section, converter transformer, smoothing reactor, filters, surge arrester, tubular bus and so on. The modeling method of valve components is based on the impedance measurements. Vector fitting is used to approximate the rational functions and Brune method is applied to provide equivalent circuits suitable for EMTP or PSCAD. The stray capacitances of the valve tower and the heat sinks are calculated by finite element method. The whole wide-band model is simulated by PSCAD/EMTDC. Based on this model, the characteristic of EMD under normal operation condition is calculated. For validity, a comparison between the simulated and measured is conducted.
出处 《中国电机工程学报》 EI CSCD 北大核心 2009年第12期24-29,共6页 Proceedings of the CSEE
基金 国家自然科学基金项目(50707008,50777017) “十一五”国家科技支撑计划重大项目(2006BAA02A20)~~
关键词 高压直流 换流站 宽频建模 电磁骚扰 high voltage DC converter station wide-band modeling electromagnetic disturbance
  • 相关文献

参考文献19

  • 1Annestrand S A. Radio interference from HVDC converter stations [J]. IEEE Trans. on Power Apparatus and Systems, 1972, 91(3): 874-882.
  • 2Sarma M P, Gilsig T. A method of calculating the RI from HVDC converter stations[J]. IEEE Trans. on Power Apparatus and Systems, 1973, 92(3): 1009-1018.
  • 3Tatro P J, Adamson K A, Eltzmann M A, et al. Power line carrier interference from HVDC converter terminals[J]. IEEE Trans. on Power Delivery, 1993, 8(3): 827-840.
  • 4Stephen A S, Devore V, Caldecott R, et al. Design and RF operation of scale model of dickson ±400kV HVDC converter station[J]. IEEE Trans. on Power Apparatus and Systems, 1985, 104(7): 1930-1936.
  • 5Robert V D, Kimball D F, Kasten D G, et al. RF analysis of a 12-pulse HVDC converter[J]. IEE Proceedings of Generation, Transmission and Distribution, 1988, 135(3): 210-218.
  • 6Caldecott R, Liu Yilu, Stephen A S, et al. Measurement of the frequency dependent impedance of major station equipment[J]. IEEE Trans. on Power Delivery, 1990, 5(1): 474-480.
  • 7Liu Y, Sebo S A, Wright S E. Modeling of converter transformer using frequency domain terminal impedance measurements[J]. IEEE Trans. on Power Delivery, 1993, 8(1): 66-72.
  • 8Ross C, Robert V D, Kasten D G, et al. HVDC converter station tests in the 0.1 to 5MHz frequency range[J]. IEEE Trans. on Power Delivery, 1988, 3(3): 971-977.
  • 9Maruvada P S, Malewski R, Wong P S. Measurement of the electromagnetic enviroment of HVDC converter stations[J]. IEEE Trans. on Power Delivery, 1989, 4(2): 1129-1136.
  • 10Dallaire R D, Maruvada P S. Evaluation of the effectiveness of shielding and filtering of HVDC converter stations[J]. IEEE Trans. on Power Delivery, 1989, 4(2): 1469-1475.

二级参考文献21

共引文献52

同被引文献296

引证文献28

二级引证文献138

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部