摘要
对运行的直燃型溴化锂制冷机充注不凝性气体,实验研究了充注不同类型及不同数量的气体后,制冷量的变化,当吸收器中不凝气体的质量分数达到9%~10%时,制冷量几乎下降50%,文中还从吸收理论讨论了本文实验结果.
This experimental research is to study the changes of refrigerating capacity in an operating direct fired Lithium Bronide absorbing chiller by purging non condensable gases of different type and quantity into the system,when non condensable gases in the absorber reach 9%~10%,refrigerating capacities will be reduced 50%.This study also discusses the experimental results from the view of the absorption theory.
出处
《湖南大学学报(自然科学版)》
EI
CAS
CSCD
1998年第2期65-69,共5页
Journal of Hunan University:Natural Sciences
关键词
不凝性气体
溴化锂吸收式
制冷机
制冷量
non condensable gas,Lithium Bronide absorbing chiller,refrigerating capacity