集中设置滤波器解决谐波倒灌的方案论证

Solution demonstration of preventing harmonics back pour by central installing filters
下载PDF
导出
摘要 针对谐波源相对集中时就地安装滤波器容易出现谐波倒灌的问题,提出了一种集中设置滤波器解决谐波倒灌的方案。结合特征值灵敏度和灰色关联分析法,解决了多支路滤波器组集中安装的问题,并用遗传算法优化滤波器的参数。在集中设置滤波器的安全校验条件中,采用求和指数确定节点谐波电压,并通过一15节点系统的实例分析,证实了采用该方法的有效性。 Since that in stalling filter locally leads to harmonic back pour when the harmonic sources concentrate, one program preventing harmonic back pour by installing filters intensively was proposed in this paper. According to the eigenvalue sensitivity and grey relative analysis method, the installation of multiple-branch filter group is realized, the filter parameters were optimized through genetic algorithm, and the summation index was applied for determining nodes harmonic voltage. In addition, the validity of this plan was verified, through analyzing an fifteen-nodes system.
作者 周阮瑜
出处 《上海电力》 2009年第2期129-132,共4页 Shanghai Electric Power
关键词 谐波抑制 滤波器配置 特征值灵敏度 灰色关联分析 harmonic suppression filter configuration eigenvalue sensitivity gray relative analysis.
  • 相关文献

参考文献4

二级参考文献13

  • 1西川 三官.最适化[M].东京:岩波书店,1982..
  • 2王兆安 杨君 等.谱波抑制与无功功率补偿[M].北京:机械工业出版社,1999..
  • 3吴竞昌(WU Jing-chang).供电系统谐波(Harmonic in Power Supply System)[M].北京:中国电力出版社(Beijing:China Electric Power Press),1998..
  • 4.GB/T14593-93.电能质量--公用电网谐波[S].,..
  • 5李群,全国高校电力系统及其自动化专业第十二届学术年会论文集,1996年
  • 6马晋--,中国电机工程学报,1995年,15卷,5期,347页
  • 7Chu R F,IEEE Trans Power Delivery,1994年,9卷,3期,1558页
  • 8团体著者,电能质量公用电网谐波,1993年
  • 9马大铭,朱东起,谢磊.综合电力滤波系统中无源滤波器的优化设计[J].电工电能新技术,1997,16(3):1-4. 被引量:23
  • 10李珊君,滕福生.有谐电网无功优化的灵敏度分析法[J].四川大学学报(工程科学版),2000,32(2):81-84. 被引量:6