110kV良容线电缆终端故障分析 被引量:1

Accident Analysis of Power Cable Terminal on 110kV Liangrong Line
下载PDF
导出
摘要 为确定佛山供电局110kV良容线电缆终端主绝缘击穿的原因,对该电缆终端头进行解剖和材料切片检查分析。分析结果认为:施工不当造成电缆绝缘屏蔽层受损,引发电场畸变严重,是引起事故的主要原因;接头的安装工艺不当引起接头受潮和接触不良,加速了主绝缘击穿的进程。建议在多雨地区,接头铜尾管与铝波纹护套的密封连接采用搪铅方式。 In order to determine the reason for main insulation breakdown of power cable terminal on 110 kV Liangrong Line under Foshan Power Supply Bureau, the anatomy of the cable terminal and the slice inspection analysis of material are carried out. It is concluded that the main reason is the damage of the insulation shielding layer of cable caused by improper construction and the ensuing serious electric field distortion: the damp of joint and the poor contact caused by improper installation of joint accelerate the main insulation breakdown. Finally it is suggested that the lead seal should be used for joining the copper tailpipe and corrugated aluminum sheath in the rainy area.
作者 武利会
机构地区 佛山供电局
出处 《广东电力》 2009年第5期67-69,共3页 Guangdong Electric Power
关键词 电缆终端 电场畸变 主绝缘击穿 cable terminal electric field distortion main insulation breakdown
  • 相关文献

参考文献4

二级参考文献6

  • 1Kaminaga K, et al. Research and development of 500kV XLPE cables[C], conference record of 1986 IEEE International Symposium on Electrical Insulation. [s 1. ], 1986, 29-36.
  • 2Fukawa M, et al. Development of 500 kV XLPE cables and accessories for long distance underground transmission line--part Ⅲ electrical properties of 500 kV cables[J]. IEEE Trans PWRD, 1996, 11(2): 627-634.
  • 3刘荣生,电工技术学报,1987年,4期,1页
  • 4邱毓昌,高压电器,1985年,5期,38页
  • 5倪光正,西安交通大学学报,1984年,18卷,4期,87页
  • 6李忠华,尹毅,朱军,屠德民.自由基清除剂类电压稳定剂的温度和浓度效应[J].电工技术学报,1999,14(1):40-44. 被引量:7

共引文献22

同被引文献16

引证文献1

二级引证文献78

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部