摘要 本文讨论了寒冷地区新风机组冬季被冻坏的原因及传统解决方法的问题,提出了空气热泵新风机组节能防冻新方法,即利用热泵冷凝器回收排风废热以加热引入室内新风。新系统的运行经验表明,各种温度随时间的变化趋于稳定,热泵的平均COP=3.7—4.6,节约电能达52%~84%,解决了防冻问题并改善了室内空气质量。 The causes of fresh air unit freezing in severe cold regions are analyzed. Several existing anti - freezing measures are discussed. A kind of new heat pump unit is designed, that inducts exhaust air into the heat pump evaporator in order to recover exhaust energy and heat fresh air. The results showe that, in the same surroundings and electricity, various temperature profiles tended to be stable, the heat pump average COP is equal to 3.7 - 4.6, electricity saving is 52% - 84%, anti - freezing problem has been solved and indoor air quality has been improved.
出处 《节能技术》 CAS 2009年第3期233-235,246,共4页 Energy Conservation Technology
关键词 寒冷地区 空气源热泵 新风机组 防冻 节能 severe cold region air - source heat pump fresh air unit anti - freezing energy conservation
  • 相关文献

参考文献5

  • 1毕雨,焦云凤,吴勇.空调机组的防冻措施[J].医药工程设计,2002,23(6):21-22. 被引量:3
  • 2夏喜英,王建华.寒冷地区通风空调新风加热器防冻问题[J].暖通空调,2002,32(4):116-117. 被引量:20
  • 3郭海丰,王思平,杜艳新,王举坤,李殊凡,石功涛.寒冷地区集中空调系统新风机组防冻措施[J].沈阳建筑工程学院学报(自然科学版),2003,19(3):218-220. 被引量:14
  • 4Chunqing WANG, Chunyu RAN, Lan ZHANG.Analysis of Using Airsource Heat Pump With Exhaust Heat Recovery in the Cold Regions. Proceedings of The 6th International Symposium on Architectural Interchanges in Asia [ C ] . Daegu, Korea. 2006, October, 25 - 28 : 857 - 862.
  • 5Chunyu RAN, Chunqing WANG, Fenghua GE, Lan ZHANG. Research on the Airsource Heat Pump Application in Cold and Sever Regions. Proceedings of Clima 2007 WellBeing Indoors[ C]. Finland, Helsinki. 2007, June, 10 - 14:223 - 229.