3/2接线方式同杆双回线路准三相运行相关保护的实现 被引量:3

Realization of the interrelated protection on quasi-three-phase running of double circuit lines on the same tower for the 3/2 circuit breaker connection
下载PDF
导出
摘要 在自适应重合闸方案的基础上,准三相运行方案能在跨线永久故障情况下,最大限度地维系两侧系统的联系。提出了利用横联光纤通道交换两回线的保护信息,线路保护装置能够实现双回线路的准三相运行。通过交换同步后的模拟量数据,把两回线健全的准三相做为一个整体配置一套保护,能够实现准三相运行方式下保护的完整性,并提出了适应准三相运行方式的三相不一致保护的新方案。 On the basis of adaptive reclosing plan, quasi-three-phase running plan can hold the relation of the two sides system farthest at the status of cross-line permanent fault. This paper uses transverse optical fiber channel commute information of double circuit lines, so the protection device can realize quasi-three-phase running of double circuit lines. After quasi-three-phase running , the protection device protects quasi-three-phase through commute synchronized sample data of double circuit lines, can realize integrality of protection. A new method of three-phase inconsistent protection for quasi-three-phase running is proposed as well.
机构地区 许继电气公司
出处 《电力系统保护与控制》 EI CSCD 北大核心 2009年第11期32-35,共4页 Power System Protection and Control
关键词 同杆双回线 自适应重合闸 准三相运行 横联光纤通道 三相不一致保护 double circuit lines on the same tower adaptive reclosing quasi-three-phase running transverse optical fiber channel three-phase inconsistent protection