期刊文献+

超大型火力发电机组冷却水泵优化配置 被引量:1

Optimization of cooling water pump in super-large thermal power units
下载PDF
导出
摘要 为了达到节能降耗的目的,对火力发电厂1000MW机组冷却水系统1台机组配3台冷却水泵单元制、1台机组配2台冷却水泵单元制和扩大单元制3种配置进行技术经济比较。从工程费用、冷却水泵的年耗电量及发电机组的微增出力几个方面综合分析讨论认为:1台机组配3台冷却水泵单元制冷却水系统对于双背压凝汽器的超大型机组是较为经济合理的冷却水泵配置和运行方式。 For purpose of energy-saving and cost-reducing, three cooling water pumps for one unit system, two cooling water pumps for one unit system and expanding unit system of 1 000 MW thermal power units were compared in technology and economic. By generally analyzing and discussing on construction costs, annual electrical power consumption of the cooling water pumps and output correction of units, the conclusion was that three cooling water pumps for one unit system would be more economical and rational on scheme and operating for super-large power units with a dual-pressure condenser.
机构地区 西北电力设计院
出处 《中国电力》 CSCD 北大核心 2009年第6期11-14,共4页 Electric Power
关键词 冷却水泵 单元制 扩大单元制 年总费用 年耗电费用 凝汽器面积 冷却倍率 cooling water pumps unit system expanding unit system annual general expense annual electrical power consumption expense condenser area cooling water ratio
  • 相关文献

参考文献3

  • 1王良中,王增顺,杨平正,等.电力工程水务设计手册[M].北京:中国电力出版社.2005.
  • 2杨护洲,杨平正,谢金根.循环水系统优化计算程序CWOV3.2用户操作手册[R].西北电力设计院,1995.
  • 3杨平正.大型机组多背压凝汽器的研究[R].西安:西北电力设计院,2006.

共引文献3

同被引文献4

引证文献1

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部