期刊文献+

压差控制对变流量空调水系统水力稳定性的影响 被引量:12

Effect of pressure difference control on hydraulic stability of variable flow air conditioning water systems
下载PDF
导出
摘要 分析了异程系统干管压差控制、异程系统末端压差控制、同程系统干管压差控制、同程系统末端压差控制、环形管网干管压差控制和环形管网末端压差控制对变流量空调水系统水力稳定性的影响。计算结果表明,同程系统、环形管网末端压差控制具有最好的水力稳定性。 Analyses the effect of different pressure difference control methods on hydraulic stability of variable flow air conditioning water systems, including main pipe pressure difference control and end pressure difference control of direct return system, reversed return system and loop pipe network. The results indicate that end pressure difference control of reversed return system and loop pipe network makes the most desirable hydraulic stability.
出处 《暖通空调》 北大核心 2009年第6期63-66,共4页 Heating Ventilating & Air Conditioning
关键词 变流量系统 末端压差控制 干管压差控制 水力稳定性 variable flow system, end pressure difference control, main pipe pressure difference control, hydraulic stability