期刊文献+

1000kV特高压长治站110kV并联电容器组技术创新及运行分析 被引量:8

Technology Innovation and Operation Analysis of 110kV Shunt Capacitor Bank in Changzhi 1000kV Ultra-high Voltage Station
下载PDF
导出
摘要 1000 kV交流特高压长治变电站110 kV并联电容器组具备容量大、电压等级高等特点,为了确保装置安全运行的要求,针对并联电容器组运行时产生操作过电压以及不平衡保护误动的现象,采用了双重操作过电压保护即防重燃的高性能断路器和过压阻尼装置并配合使用双桥差不平衡电流保护等技术创新措施,从而有效的抑制了上述问题的产生,并在文章最后提出了在运行维护中需注意的问题。 The 110 kV shunt capacitor banks in station characterized in large capacity and high vq and aiming to the phenomena of switching overv Changzhi 1 000 kV UHV(Ultra-high Voltage) suboltage. Making sure the safe operation of the device oltage and unbalance protection malfunction, some technical innovation measures were used such as double switching overvoltage protection (using low restriking circuit breaker and over damping device ) and double differential current bridges. The result shows that the above problems are effectively restricted when shunt capacitor banks are running normally. Finally, the paper makes an additional description of the installation in operation and maintenance issues that need attention.
出处 《电力电容器与无功补偿》 2009年第3期9-13,共5页 Power Capacitor & Reactive Power Compensation
关键词 特高压 并联电容器组 操作过电压 双桥差 技术创新 运行维护 UHV Shunt capacitor bank Switching overvohage Double differential current bridges Technical innovation Operation and maintenance
  • 相关文献

参考文献8

  • 1中国电力工程顾问集团.1000kV晋东南-南阳-荆门特高压交流试验示范工程初步设计专题研究报告[R].2007.
  • 2中国电力工程顾问集团.特高压交流试验示范工程容性无功补偿装置配置方案专题研究[R].2007.
  • 3梁琮.双桥接线-特大型电容器组的最佳选择[A].110kV双桥差并联电容器成套装置技术资料汇编[C].2007.
  • 4陕华平.1000kV晋东南-南阳-荆门特高压交流试验示范工程110kV低压无功补偿装置的配置及运行分析.国网运行,2008,(13).
  • 5IECTC33-149.并联电容器及低压并联电容器组保护导则[S].2007.
  • 6SDJ25-1985.并联电容器装置设计技术规程[S].2007.
  • 7IEEE C37.99 - 2000. IEEE Guide for Protection of Shunt Capacitor banks[ S]. 2000.
  • 8IEEE1036 - 1992. IEEE Guide for Application of Shunt Power Capacitors [ S ]. 2003.