期刊文献+

1000kV特高压交流变电金具电晕特性及优化 被引量:17

Corona Characteristics and Optimizing of 1000 kV UHVAC Substation Fittings
下载PDF
导出
摘要 1000kV特高压交流变电站运行电压很高而且相邻电场会相互影响,使得变电金具的设计比以往线路金具的设计要求更高、更复杂。为了让应用于特高压交流试验示范工程的变电金具拥有良好的高压电气特性,以国家电网公司特高压交流试验基地为样本,对变电站各种主要金具表面场强进行了仿真计算研究,对不同结构的金具进行了初步的优化设计,并采用科学的金具试验方法对各种优化后的不同结构的金具进行了电晕试验研究,根据试验结果提出了优化金具的建议意见,采纳该建议设计的试验示范工程变电站金具满足运行要求。 The design of fittings in the 1000 kV UHVAC substation becomes more difficult and complex, because of the higher operating voltage and interaction of the electric field nearby. In order to make substation fittings used in the UHVAC demonstration project have better electrical performance, the simulating models were established according to the first UHVAC test base of SGCC, then the surface electric field of the primary substation fittings was calculated, finally, the optimized fittings was obtained. Furthermore, the corona tests for the optimized fittings of different configuration with scientific and objective methods were carried out. Through these research results, the paper indicated further optimizing views, and the ultimate designed fittings could meet the requirement of the UHVAC demonstration project well.
出处 《高电压技术》 EI CAS CSCD 北大核心 2009年第6期1237-1242,共6页 High Voltage Engineering
基金 国家电网公司科技项目(SGTGY[2009]612)~~
关键词 特高压 特高压交流实验基地 变电金具 仿真计算 电晕特性 优化 紫外线 紫外成像仪 母线金具 终端球 耐张串 UHV UHVAC test base substation fittings simulation calculation corona characteristic optimizing ultraviolet radiation corona camera bus-bar fittings corona ball tension insulator strings
  • 相关文献

参考文献13

  • 1彭宗仁,高乃奎,刘学忠,等.750kV紧凑型输电线路绝缘子串电位分布及均压环优化配置研究[R].北京:国家电力公司,2002.
  • 2陈勇,谢雄杰,谢梁,谷莉莉,霍锋,彭宗仁.750kV同塔双回紧凑型线路均压环的优化研究[J].高电压技术,2008,34(11):2390-2394. 被引量:10
  • 3国网武汉高压研究院.1000kV特高压变电站母线结构及配套金具的优化研究[R].武汉:国网武汉高压研究院,2008.
  • 4刘云鹏,杨迎建,蔡炜,等.紫外成像检测技术在交流特高压试验基地的应用[c]//输电线路紫外检测技术交流会文集.武汉:中国电机工程学会输电线路专业委员会,2007.
  • 5汪涛,阮羚,邓万婷,等.特高压交流试验基地1000kV设备电晕监测分析[C]∥输电线路紫外检测技术交流会文集.武汉:中国电机工程学会输电线路专业委员会,2007.
  • 6迟殿林,曾庆立.用紫外成像检测电气设备外绝缘状况[J].东北电力技术,2005,26(1):22-23. 被引量:36
  • 7杨迎建,刘云鹏,万启发,等.基于紫外成像检测技术的特高压均压环起晕电压试验研究[C]//输电线路紫外检测技术交流会文集.武汉:中国电机工程学会输电线路专业委员会,2007.
  • 8Arbusov R S, Ovsyannikov A G. UV inspection of HV equipment[C]// Proceedings of the XIVth International Symposium on High Voltage Engineering. Beijing, China: Tsinghua University, 2005.
  • 9Lindner M, Elstein S, Lindner P, et al. Daylight corona discharge imager[C] //Eleventh International Symposium on High Voltage Engineering. London, UK: Ofil Ltd, 1999.
  • 10万启发,陈勇,谢梁,胡伟,霍锋,孟刚,刘云鹏,许中,谷莉莉.特高压交流输变电工程设备的电晕试验[J].高电压技术,2007,33(3):14-16. 被引量:28

二级参考文献42

共引文献97

同被引文献235

引证文献17

二级引证文献129

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部