期刊文献+

二次滤波器组操作断路器的额定电压选取

Slection of Voltage Rating for Operating Circuit Breaker of Secondary Filter Bank
原文传递
导出
摘要 针对二次滤波器组在开断时断口恢复电压过高而易发生重击穿的问题,根据IEC56和GB7675关于断路器开断电容器的有关规定,提出了选用比系统电压等级更高的断路器作为其操作断路器,并提出了选用断路器额定电压等级的原则。 In view of the frequent occurrence of restrikng of contacts in the circuit breaker of the secondary filter bank due to excess of recovery voltage during breaking operation, the selection of a circuit breaker with higher voltage grade than that of the system for the filter bank is recommended according to the requirement for open/close of the capacitor bank of the circuit breaker in IEC 56 and GB 7675, and the selection principle of the rating voltage for the circuit breaker is also suggested.
作者 林启文
出处 《华东电力》 1998年第7期1-4,共4页 East China Electric Power
关键词 二次滤波器组 断路器 额定电压 炼钢 电弧炉 2nd filter bank circuit breaker rated voltage recovery voltage
  • 相关文献

参考文献1

二级参考文献3

  • 1谷定燮,孙浩良,秦连城,徐贵林.并联补偿电容器组过电压保护方式的研究[J]高电压技术,1988(02).
  • 2谷定燮,孙浩良,秦连城,徐贵林.氧化锌避雷器限制切并联电容器过电压效果及其能量计算的研究[J]高电压技术,1987(02).
  • 3张学鹏,苏树庚.大型自动调压电容器组过电压保护及其保护元件的试验研究[J]高电压技术,1983(02).

共引文献11