摘要
针对发电机失磁引起的危害,分析了发电机失磁保护误动原因,并介绍了整流型抛球圆特性阻抗失磁继电器(LZ-2型)工作原理、阻抗特性及发电机失磁保护整定计算、调试方法。结果验证了采用继电器定值调节配置方案的可行性,可获得最小精确工作流量、防止误动。
Aimed at danger of loss of generator excitation,the cause of malfunction is analyzed. The working principle, impedance characteristic setting calculation and debugging method of a rectified type loss of generator excitation relay with round drop characteristic(LZ-2 type)are introduced. The results validate the feasibility of configuration scheme by use of relay setting configuration. Minimum precise working current and malfunction prevention are obtained.
出处
《水电能源科学》
北大核心
2009年第3期202-205,共4页
Water Resources and Power
关键词
失磁保护
LZ-2失磁继电器
阻抗特性
整定计算
调试方法
loss of excitation protection
LZ-2 loss of excitation relay
impedance characteristic
setting calculation
debugging program