摘要 针对临沂供电公司GIS组合电器事故,运用常规与非常规化学、电气试验手段,对GIS SF6CT气室中闪络故障前后气体成分及CT气室内的材料进行排查试验,分析了事故原因,指出事故是由内置式CT气室内的丁腈橡胶板中的腐蚀性硫与气室内触头等镀银件反应形成硫化银,最终形成导电通道,引起CT气室闪络击穿。并提出了预防发生此类事故的具体措施。 Recently, flashover faults of GIS occur frequently in power supply systems. Examinations based on chemical and electrical experiments were carried out on the gas components and chemical materials in CT air chamber before and after happening of flashover faults. It shows that it is the corrosive sulfur existing in the butyronitrile rubber plate of CT air chamber reacts with the silver plated contacts inside CT air chamber and produce silver sulphide, thus forming an electrical path and causing flash over faults. Some measures to prevent the accidents were proposed.
出处 《绝缘材料》 CAS 北大核心 2009年第3期67-68,72,共3页 Insulating Materials
关键词 组合电器 六氟化硫 组分分析 闪络击穿 gas-insulated switchgear (GIS) sulfur hexafluoride (SF6) component analysis flash over
  • 相关文献

参考文献3

二级参考文献21

  • 1刘先勇,周方洁,胡劲松,李红雷.光声光谱在油中气体分析中的应用前景[J].变压器,2004,41(7):30-33. 被引量:40
  • 2王书涛,车仁生,王玉田,田庆国.基于光声光谱法的光纤气体传感器研究[J].中国激光,2004,31(8):979-982. 被引量:11
  • 3张川,王辅.光声光谱技术在变压器油气分析中的应用[J].高电压技术,2005,31(2):84-86. 被引量:48
  • 4马虹斌,邱毓昌.SF_6及其混合气体的放电毒性污染物分析[J].环境工程,1996,14(4):46-48. 被引量:8
  • 5罗学琛.SF6气体绝缘全封闭组合电器(GIS)[M].北京:中国电力出版社,1998..
  • 6Piemontesi M, Niemeyer L. Sorption of SF6 and SF6 decomposition products by activated alumina and molecular sieve 13X[C].IEEE International Symposium on Electrical Insulation. Montreal, Quebec, Canada, 1996: 828-838.
  • 7Beyer C, Jenett H, Klockow D. Influence of reactive SFx gases on electrode surfaces after electrical discharges under SF6 atmosphere[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2000,7(2): 234-240.
  • 8Qiu Y, Kuffel E. Comparison of SF6/N2 and SF6/CO2. gas mixtures as alternatives to SF6 gas[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1999, 6(6): 892-895.
  • 9Isidor Sauers. Evidence for SF4 and SF2 formation in SF6 corona discharges[R]. Tennessee, USA: IEEE, 1991.
  • 10Derdouri A, J Casanovas. 3 Spark decomposition mixtures of SF6/H2O [J]. IEEE Transactions on Electrical Insulation, 1989, 24(6): 1147-1157.