期刊文献+

500kV变电站遵循IEC61850标准统一建模 被引量:6

Unified modeling of 500kV substation according to IEC61850
下载PDF
导出
摘要 500kV桂林变电站的间隔层、变电站层全部遵循IEC61850标准统一建模。500 kV桂林变电站采用PS6000+变电站自动化系统,通过IEC61850通信协议实现变电站层对间隔层数据的监视和控制。该工程除了直流屏等少数不具备网络通信能力的装置外,整个系统取消了规约转换器,各智能设备间完全采用IEC61850规约通信;远动通信服务器对间隔层IEC61850通信使用双网热备用模式,而后台监控则实现了双网双工;各测控装置的间隔层联闭锁则基于GOOSE组播数据共享而实现。 Both station and bay levels of 500 kV Guilin substation are modeled according to IEC61850 standard. Its PS 6000^+ substation automation system adopts IEC61850 protocol to implement the supervision of bay level data. Except a few devices without network communication ability,all IEDs directly communicate with each other according to IEC61850,without any protocol converter. Dual-network hot-backup mode is used in IEC61850 communication between telecontrol communication server and bay unit,while dual-network duplex mode is used in background monitoring. Bay level interlock among measuring and control devices is based on data sharing by GOOSE multicasting.
作者 刘琳 胡道徐
出处 《电力自动化设备》 EI CSCD 北大核心 2009年第7期113-117,共5页 Electric Power Automation Equipment
关键词 500 KV变电站 变电站自动化系统 IEC61850标准 双网冗余 通信网络 500 kV substation substation automation system IEC61850 standard dual network redun- dancy communication network