期刊文献+

一种交流进线备自投的设计及实现 被引量:1

Design and implementation of a AC incoming line for spare power automatic-switching device
下载PDF
导出
摘要 为提高某重要10kV配电室供电可靠性,针对其双回10kV电源进线,结合进线柜内原有控制回路,利用交流继电器,以10kV母线三相失压为备自投启动元件,设计一种交流进线备自投装置,以确保10kV配电室安全可靠地供电。 To enhance power supply reliability of an important 10 kV distribution room, this paper checks its double circuit 10kV source lines, combines the original cabinet line-loop control, and uses the AC relays. It takes 10 kV bus three-phase voltage loss as its device start element, and designs a AC incoming line for spare power automatic swiching device to ensure safe and reliable power supply of the 10 kV power distribution room.
作者 李波
出处 《电力系统保护与控制》 EI CSCD 北大核心 2009年第14期109-111,共3页 Power System Protection and Control
关键词 10kV配电室 供电可靠性 交流继电器 10kV母线三相失压 交流进线备自投 10 kV power distribution room power supply reliability AC relay 10 kV three-phase bus lost pressure AC incoming line for automatic device