期刊文献+

干工况风机盘管机组性能实验研究 被引量:10

Experimental study on a fan-coil unit running in dry conditions
下载PDF
导出
摘要 采用焓差法对某风机盘管机组在供水温度为14~18℃、供回水温差为3℃的条件下进行了实验,研究了露点温度附近干、湿工况分界区域的性能。实验结果表明,被测机组的供冷量随供水温度升高而迅速下降,随送风量减少而下降。干工况风机盘管机组的最佳供水温度为17℃,宜采用高挡风量运行。风机盘管干工况运行供冷量比标准工况下降2/3。 With the air enthalpy difference method, tests a fan-coil unit running in the conditions where the supply water temperature is 14 to 18 ℃, the temperature difference is 3 ℃, and studies the critical point from dry to wet conditions. The results show that cooling capacity of the unit drops dramatically as the supply water temperature rises, and also drops as the supply air rate decreases. For the fan-coil unit running in dry condition, the most suitable supply water temperature is 17 ℃, and it is better to run at high speed condition for the supply air rate. The cooling capacity of the fan-coil unit running in dry condition drops 2/3 than in the standard condition.
机构地区 广州大学
出处 《暖通空调》 北大核心 2009年第7期1-4,共4页 Heating Ventilating & Air Conditioning
关键词 风机盘管机组 干工况 供水温度 送风量 供冷量 fan-coil unit, dry condition, supply water temperature, supply air rate, cooling capacity
  • 相关文献

参考文献3

二级参考文献29

  • 1殷平.机器露点实验研究(一)──水冷式表冷器机器露点研究[J].通风除尘,1997,16(1):11-14. 被引量:10
  • 2井上宇市 范存养等(译).空气调节手册[M].北京:中国建筑工业出版社,1986..
  • 3清华大学.空气调节(第2版)[M].北京:中国建筑工业出版社,1985.113-114.
  • 4孙格非.翅片盘管(水冷)热工计算新方法[J].制冷学报,1980,(2):49-64.
  • 5俞梅琴.计算空冷器(水冷)传热系数K值的一个新的实验公式[J].暖通空调,1985,15(5):26-27.
  • 6孙格非.翅片盘管(水冷)热力计算新方法[J].制冷学报,1980,(2):49-64.
  • 7GB 50155-92采暖通风与空气调节术语标准
  • 8ASHRAE Standard 12-75 Refrigeration definitions and terms
  • 9王晋生,缪小平.表冷器机器露点含义质疑及其替换术语的提出.见:全国暖通空调制冷2000年学术年会论文集.2000.694-697
  • 10同济大学暖通教研室,上海安装公司通风队.双排热交换器热工性能测试报告.1976