期刊文献+

间歇运行对翅片管式蒸发器长效特性的影响 被引量:3

Effects of intermittent operation on long-term performance of finned coil type evaporator
下载PDF
导出
摘要 研究了翅片管式蒸发器在空调器长期运行中,由于间歇运行对于其换热和空气侧压降的影响。实验对象为一个铝翅片铜管换热器和一个铜管铜翅片换热器。实验表明,经过多次间歇运行后,蒸发器的换热系数明显下降,空气侧压降有所增大,铜翅片铜管换热器的长效换热特性强于铝翅片铜管换热器,两者的长效压降特性相当。 The effects of long - term intermittent operation on the air - side heat transter and pressure urop performance of finned coil type evaporators of air conditioners are investigated by experiments on an aluminum - fin evaporator and a copper - fin evaporator. The test results indicate that the air - side heat transfer coefficient decreases and the pressure drop increases after a long - term intermittent operation, and the influence of long - term intermittent operations on heat transfer coefficient of the aluminum - fin evaporator is larger than that of the copper - fin evaporator while the influence of the long term intermittent operation on the pressure drop of both type evaporators are identical.
出处 《制冷技术》 2009年第2期29-33,共5页 Chinese Journal of Refrigeration Technology
关键词 蒸发器 换热 压降 间歇运行 evaporator, heat transfer, pressure drop, intermittent operation
  • 相关文献

参考文献5

  • 1J.C.Min,R.L.Webb,C.H.Bemisderfer.Long-term hydraulic perfomance of dehumidifying heat exchangers with and without hydrophilic coatings[J].HVAC and R Research,2006,(2):257-272.
  • 2Yang,L.,Braun,J.E.,Croll,E.A.,Impact of fouling on the performance of filter-evaporator combinations[J].International Journal of Refrigeration,2007,30(3):489-498.
  • 3中国家用空调器使用习惯研究[R].国际铜业协会报告,2006.
  • 4C.C.Wang.Data reduction for air-side performance of fin-andtube heat exchangers[J].Experimental Thermal and Fluid Science.2002,21(4):218-226.
  • 5K.T.Hong.Fundamental characteristics of the dehumidifying heat exchangers with and without the wetting coatings[D].PhD thesis.The Pennsylvania State University,University Park,PA.1996.

同被引文献24