期刊文献+

Fault location for parallel transmission lines using one-terminal current traveling waves

Fault location for parallel transmission lines using one-terminal current traveling waves
下载PDF
导出
摘要 With proper phase module transformation,parallel lines can be decomposed to the same directional net and the reverse directional net. The propagation characteristics of traveling waves in the reverse directional net were analyzed,and the refraction coefficient at the fault point for a single phase fault was derived. In addition,the module selection was discussed. Simulation results show that satisfying accuracy can be achieved with the proposed method. Moreover,it is immune to fault types,fault resistances,and outside system parameters. With proper phase module transformation, parallel lines can be decomposed to the same directional net and the reverse directional net. The propagation characteristics of traveling waves in the reverse directional net were analyzed, and the refraction coefficient at the fault point for a single phase fault was derived. In addition, the module selection was discussed. Simulation results show that satisfying accuracy can be achieved with the proposed method. Moreover, it is immune to fault types, fault resistances, and outside system parameters.
作者 徐青山
出处 《Journal of Harbin Institute of Technology(New Series)》 EI CAS 2009年第3期408-412,共5页 哈尔滨工业大学学报(英文版)
基金 Sponsored by the Ph.D. Programs Foundation of Ministry of Education of China(Grant No.20070286047) the Scientific Innovation Foundation forYoungster of CSEE
关键词 故障测距 平行线 输电线路 行波 电流 单端 相模变换 传播特性 fault location parallel transmission lines traveling wave reverse directional net
  • 相关文献

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部