摘要
1997年6月北京某写官楼员工发生一起上呼吸道感染样(上感样)疫情。为查明爆发原因,采用流行病学病例-对照调查研究方法,分别对病例组、对照组进行嗜肺军团菌(Lp)抗体-1 ̄14型血清学检测,并对大厦空调系统采们进行细菌学培养检测。结果:该次爆发疫情的扁桃体炎罹患率为61.86%,上感罹患率34.62%,统计学检验发热与扁体关系密切(X^2=77.88,P〈0.01);上感病例LP9、10、12。
An outbreak of upper respiratory infection (influenza-like syndrom) took place among the staff members of a large office building in Beiiing, June, 1997. To understand the cause of the outbreak, with a case-control study with serological antibodies detection against serogroup 1 to 14 of Legionnaires' disease bacteria (LDB) and bacteriological test and culture on samples collected from the air-conditioning system of the office building was performed. The findings showed that the attack rates of tongillitis and upper respiratory infection were 61.86% and 34.62% respectively. The relation was statistically significant between the symptoms of fever and tonsillitis in the cases (χ~2 =77.88, P<0.01). The positive rates of LDB antibodies on serogroups 9, 10, 12, 14 were 45.94% in the cases of upper respiratory infection and 3/15, 6/17, 0/15, 1/16 respectively in the four controls groups. Condensied water samples from an air-conditioning system showed that Legionella Pneumophila was positive. Evidence showed that it was an outbreak resulting from LDB serogroup 9 and 12, accompanied by upper respiratory infection related to air-conditioning system contaminated by LDB. This was the first report Lp infection associated with an air-conditioning system in Cbina.
出处
《中华流行病学杂志》
CAS
CSCD
北大核心
1998年第4期200-204,共5页
Chinese Journal of Epidemiology
关键词
军团病
空调系统
流行病学
上呼吸道感染
Legionnaires' disease Air-conditioning system Outbreak epidemic