空气湿度对导线电晕起始电压的影响 被引量:23

Influence of Humidity on Conductor Corona Onset Voltage
原文传递
导出
摘要 我国特高压工程中,输电线路要经过山地、湖泊等高湿度地区,空气湿度对架空输电线路电晕放电有较大影响。为研究湿度对导线电晕放电的影响,利用同轴线-筒电极研究了不同大气湿度对交流以及直流正负极性电晕起始电压的影响规律。试验结果表明:湿度对直流正极性电晕起始电压影响较小,而对直流负极性以及交流电压电晕起始电压影响较大:在相对湿度达50%~60%时,直流负极性与交流起晕电压最高。分析认为,空气湿度对空间电荷分布的影响以及湿度对导线表面状态的影响是导致起晕电压变化的主要因素。 UHV transmission lines in China may cross some high humidity areas such as lakes and mountains. Air humidity has great effect on corona performance of transmission lines. In this paper, AC and DC corona onset voltage under different air humidity was studied with the line-cylinder electrode. The results show that the change of the air humidity has slight effect on positive DC corona onset voltage. But the change of the air humidity has an obvious effect on AC and negative DC corona onset voltages. The AC and negative DC corona onset voltages are highest when the relative air humidity is about 50%-60%. The influences of humidity on space charge distribution and the rough rate of the electrode surface are the main reasons that may cause the corona onset voltage changes with air humidity.
出处 《电力建设》 2009年第8期38-41,共4页 Electric Power Construction
基金 国家电网公司科技项目(SGSC[2005]81)
关键词 空气湿度 电晕 起晕电压 air humidity corona corona onset voltage
  • 相关文献

参考文献11

  • 1周浩,余宇红.我国发展特高压输电中一些重要问题的讨论[J].电网技术,2005,29(12):1-9. 被引量:266
  • 2邬雄,聂定珍,万保权,等.交流特高压输电工程环境影响问题的基础研究[R].武汉:武汉高压研究所,2001.
  • 3毛文奇,刘海燕,徐华,黄文武.特高压输电对环境影响的讨论[J].电力建设,2004,25(8):54-56. 被引量:28
  • 4范建斌,谷琛,李军,宿志一,李中新,何宝龙,殷禹,甘伦,徐世山,康钧.±800kV典型直流设备电晕起始电压的海拔校正方法[J].中国电机工程学报,2008,28(25):8-13. 被引量:33
  • 5Nayak S K,Thomas M J.An integro-differential equation technique for the computation of tadiated EMI due to corona on HV power transmission line[J].IEEE Trasactions on Power delivery,2005,20 (1):488-493.
  • 6D B Philips,R.G Olsen,P D Pedrow.Corona onset as a design optimization criterion for high voltage hardware[J].IEEE transactions on dielectric and electrical insalation,2000,11:744-751.
  • 7Van Brunt RJ.Physics and chemistryof partial discharge and corona[J].IEEE Transactions on Dielectrics and Electrical Insulation,1994,1(5):761-784.
  • 8A.A.AI-Arainy,N.H.Malik.Statistical variation of ac coronap pulse amplitudes in point-to-plane air gaps[J].IEEE Transaction on Electrical Insulation,1989,24(4):681-687.
  • 9N.L.Allen,M Abdel-Salamand I.Cotton.Effects of temperature and pressure change on positive corona and sparkover under direct voltage in short airgaps[J].IET sci.techaol,2007,1(4):210-215.
  • 10Trichel G W.The mechanism of the negative point to plane corona onset[J].physical Review,1938.

二级参考文献70

共引文献355

同被引文献247

引证文献23

二级引证文献132

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部