电网谐波对消弧线圈接地系统的影响 被引量:8

The Impact of Power Grid Harmonics on Grounding System of Arc-suppression Coil
下载PDF
导出
摘要 为验证某制造厂新型自动调谐消弧线圈装置性能,笔者进行了消弧线圈成套装置金属接地、电阻接地、弧光接地等现场试验,结果发现,当电网具有较高谐波时,单相接地电流含有丰富的谐波成分,消弧线圈并不能补偿谐波接地电流,造成以谐波为主的残流值超标,影响补偿效果,对此问题应引起关注。 In order to test the performance of new type automatic tuning arc-suppression coil of some factory, the metal grounding, resistance grounding and arc grounding test of arc-suppression coil whole set tests were carried out. By analyzed the test result, abundant harmonic component was discovered in single-phase grounding current when power grid have more harmonics, and arc-suppression coil can not compensate for harmonic grounding currents. This will cause harmonic residual grounding current exceed the standard value, compensation effects be affected. It needs more attention to this question.
作者 金百荣 李电
机构地区 绍兴电力局
出处 《高压电器》 CAS CSCD 北大核心 2009年第4期159-162,共4页 High Voltage Apparatus
关键词 消弧线圈 电网谐波 残流 接地系统 arc suppression coil harmonics residual current grounding system
  • 相关文献

参考文献8

二级参考文献16

  • 1陈绍英,葛栋,常挥,刘刚,韩芳,鲁铁成.配电网超低频振荡的仿真计算研究[J].高电压技术,2004,30(5):18-19. 被引量:21
  • 2石启新,谈顺涛.基于MATLAB的PT铁磁谐振数字仿真研究[J].浙江电力,2004,23(4):6-9. 被引量:3
  • 3陈飞,田园.10kV电压互感器高压熔丝频繁熔断的分析[J].高电压技术,2005,31(9):88-89. 被引量:14
  • 4[1]DL/T 620-1997,交流电气装置的过电压保护和绝缘配合[S],1997.
  • 5[1]IEEE Std 142-1991,IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems[S],1991.
  • 6[2]IEEE Std 80-2000 IEEE Guide for Safety in AC Substation Grounding[S],2000.
  • 7[5]IEC60076-11(2004-05)Dry-type transformers[S].
  • 8李福寿(LIFu-shou).中性点非有效接地电网的运行(OperationofElectricPowerSystemwithNeutralIneffectiveGrounding)[M],Hydraulic and Electric Power Press)[M].北京:水利电力出版社(Beijing,1993..
  • 9李福寿.消弧线圈自动调谐技术讲义[M].上海:上海思源电气股份公司,2002.
  • 10董其国.电能质量技术问答[M]中国电力出版社,2003.

共引文献56

同被引文献99

引证文献8

二级引证文献67

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部