期刊文献+

培养法与Equate^(TM)抗原检测法检测集中空调冷却水军团菌 被引量:2

Detection of Legionella in water of cooling tower by culture and Equate^(TM) antigen detection assay
原文传递
导出
摘要 目的:了解集中空调冷却水军团菌污染状况和血清型分布,评价利用EquateTM水军团菌快速试验试剂盒检测军团菌。方法:选取南京、常州、苏州共148家集中空调冷却塔,每个冷却塔平行采集两份水样,分别用培养法和EquateTM水军团菌快速试验试剂盒检测军团菌。结果:培养法军团菌的总阳性率为75%,共检出菌株145株,血清型分布以LP1(65.5%)为主,LP2-8、L.micdadei、L.bozemanii均有检出;EquateTM试剂盒检测LP1阳性率为57.4%,与培养法比较差异无统计学意义(McNemarχ2=1.56、P=0.26),检测灵敏度、特异度易受其他细菌干扰。结论:集中空调冷却水军团菌污染较普遍,血清型别多样以LP1为主。EquateTM水军团菌快速试验试剂盒,可作为培养法的辅助手段用于突发事件应急,筛查高浓度LP1污染,不适于常规监测。 Objective: To learn the pollute status and its serum type of Legionella in the cooling tower water of central air-conditioning and evaluate the utility of the Equate^TM water Legionglla test kit for detection of Legionella.Methods:From Nanjing,Changzhuo,Suzhuo 148 cooling towers water of central air-conditioning were recruited and measured the prevalence of Legionella by culture and the Equate^TM water Legionglla test kit.Results:The positive detective rate of culture was 75%,and 145 strains were isolated.The distribution of serum of Legionella mostly was LP1(65.5%),others were LP2-8,L.micdadei,L.bozemanii;The positive rate of LP1 by the Equate^TM test kit was 57.4%.To compare with culture,the distinction has not statistics significance(McNema χ^2=1.56,P=0.26).But the sensitivity and specificity of detection was interference by other bacteria.Conclusion:The pollution status of Legionella in central air conditioning cooling water was common,and its serotypes is manifold,the most serotype was LP1.The Equate^TM test kit could be considered as an adjunct to culture for emergency,screening of high concentration of pollution LP1,but not suitable for water environment regular monitoring of Legionella.
出处 《中国卫生检验杂志》 CAS 2009年第8期1820-1822,共3页 Chinese Journal of Health Laboratory Technology
基金 "十一五"国家科技支撑计划项目(2006BAI19B04)
关键词 军团菌 集中空调 冷却塔水 检测 Legionella Central air conditioning Cooling tower water Detection
  • 相关文献

参考文献11

  • 1Bentham RH. Routine sampling and the control of Legionella spp. in cooling tower water systems[ J ]. Curt Microbiol,2000,41 (2) : 271 - 275.
  • 2Sabria M, Alvarez J, Dominguez A, et al. A community outbreak of Legionnaires disease: evidence of a cooling tower as the source [ J ]. Clin Microbiol Infect,2006,12 ( 7 ) :642 - 647.
  • 3康晓明 汤忠群 夏锡荣.嗜肺军团菌感染1例报告.解放军医学杂志,1982,7(4):240-240.
  • 4邵祝军.军团菌病的监测与防治[J].疾病监测,2005,20(6):281-282. 被引量:34
  • 5Steinert M, Emody L, Amann R, et al. Resuscitation of viable but nonculturable Legionella pneumophila Philadelphia JR32 by Acanthamoeba castellanii[ J ]. Appl Enviro Microbiol, 1997,63 ( 5 ) :2047 - 2053.
  • 6Berdal BP, Farshy CE, Feely JC. Detection of Legionella pneumophila antigen in urine by enzyme - linked immunospeeifie assay [ J ]. J Clin Microbiol, 1979, 9:575 -578.
  • 7Marta PS, Monika CP. Occurrence and pathogenicity of the family of Legionella ceae[J]. Postepy Hig Med Dosw, 2008,62:337 -353.
  • 8Nadarajah M, Goh KT. Isolation of Legionella pneumophila from hospital cooling towers[ J]. Ann Acad Med Singapore, 1986,15:6 -8.
  • 9Koide M, Saito A, Kusano N, et al. Detection of Legionella spp. in cooling tower water by the polymerase chain reaction method[ J]. Appl Environ Microbiol, 1993, 59 : 1943 - 1946.
  • 10裘丹红,郑官增,沈伟伟,林海江,朱水荣.浙江省台州市区中央空调冷却水军团菌污染调查分析[J].中国卫生检验杂志,2007,17(7):1200-1202. 被引量:9

二级参考文献8

  • 1斯国静,俞骅,王一泓,吴小辉,杨介钻.杭州市区公共场所空调冷却水中嗜肺军团菌的调查和分析[J].中国卫生检验杂志,2006,16(3):281-282. 被引量:21
  • 2武建国.军团病[M].南京:东南大学出版社,1990.
  • 3Fields B.The molecular ecology of legionellae[J].Trends Microbiol,1996,4(7):286 -290.
  • 4Michael Steinert.Legionella pneumophila:an aquatic microbe goes astray[J].FEMS Microbiology Reviews,2002,26 (2):149-162.
  • 5Edelstein PH,Meyer RD.Legionnaires' disease[J].Chest,1984,85(1):114-120.
  • 6彭晓雯.军团病新发传染病的预防与控制[M].北京:协和医科大学出版社,2002.
  • 7公共场所集中空调通风系统卫生规范[S].2004.
  • 8万超群.军团病防治研究进展[J].疾病监测,1997,12(2):69-71. 被引量:33

共引文献51

同被引文献33

引证文献2

二级引证文献10