150MW空冷发电机运行温度高原因分析及对策 被引量:1

Cause Analysis on High Temperature Faults of a 150 MW Air-cooled Generator and the Remedy
下载PDF
导出
摘要 针对1台150 MW空冷发电机运行温度高的问题,从发电机散热方式及空气冷却器的工作机理进行了分析,指出发电机运行温度高的原因是空气冷却器换热效率的降低,而换热肋片的损坏及空气通道的杂物堵塞是空气冷却器换热效率降低的主要因素;提出了防范措施,使冷却器效率得以提高,发电机运行温度下降。 Aiming at the high temperature faults encountered by a 150 MW air-cooled generator during operation, by analyzing the heat distribution mode of generator and the working principle of air cooler, the trouble was found to be caused by low heat-exchanging efficiency of the air cooler, resulting from damage of the heat-exchanger fin and blockage in the air passage. Countermeasures were proposed and taken, after which the cooling efficiency has been raised and the generator operation temperature lowered.
作者 张新闻
出处 《发电设备》 2009年第5期370-373,共4页 Power Equipment
关键词 空冷发电机 空气冷却器 发电机损耗 换热效率 air-cooled generator cooler generator loss heat-exchanging efficiency