摘要 为研究高压交流输电线路电场短期生态效应,对其工频电场特性、短期生态效应及改善措施进行分析,并建立模型,对电场中人体感应电流及人体内部电场强度进行了计算。结果表明高压交流输电线路产生的工频电场强度为4×10~3V/m时,通过人体脚部产生的总感应电流为60μA,远低于人体伤害电流6×10~3~9×10~3μA,人体不会出现刺痛感和不舒服的感觉;人体内部产生的电场强度为0.176×10^(-3)V/m,远低于外加电场强度4×10~3V/m,人体内部产生的电场强度对外加电场强度而言是及其微弱的。 To study the short-term ecological effect of electric field under HV AC transmission line, the characteristics of its power frequency electric field and ecological effect as well as improvement measures are analyzed. Human body induced current and internal electric field strength within the electric field are calculated by building model. The results show that when power frequency electric field strength of HV AC transmission line is 4×10^3 V/m, the total induced current through human feet is 60 μA, which is far lower than the human body damage current about 6-9×10^3 μA, and the feelings of stabbing pain & comfortlessness wouldn't come out. The human body internal electric field strength is 0.176×10^-3 V/m, which is much lower than the applied one 4×10^3 V/m, and the internal electric filcd is very feeble to applied electric field.
出处 《陕西电力》 2009年第8期22-25,共4页 Shanxi Electric Power
关键词 短期生态效应 工频电场 人体感应电流 人体内部电场强度 short-term ecological effect power frequency electric field human body induced current human body internal electric field intensity
  • 相关文献

参考文献10

二级参考文献18

  • 1舒印彪,刘泽洪,袁骏,陈葛松,高理迎.2005年国家电网公司特高压输电论证工作综述[J].电网技术,2006,30(5):1-12. 被引量:215
  • 2李晓萍,文习山,樊亚东,张宇,蓝磊,陈慈萱.直流入侵三相三柱变压器励磁电流及谐波计算[J].高电压技术,2006,32(5):69-72. 被引量:26
  • 3冯慈璋.电磁场(电磁原理Ⅱ)[M].北京:人民教育出版社,1979.
  • 4国际大电网会议第36.01工作组.邵方殷译,输电系统产生的电场和磁场现象实用计算导则[M].北京:水利电力出版社,1984.
  • 5GB 4365-2003,电磁兼容术语[S].
  • 6Bionomics Research Working Group Bonneville Power Administration USA. Electrical and biological effects of power transmission line[R]. Beijing: Beijing Electric Power Research Institute Ministry of W & E, 1987.
  • 7Schmidt G, Fiegl B. HVDC transmission and the environment [J]. IEEE Trans on Power Engineering Journal, 1996, 10 (5) 204-210.
  • 8IEEE Working Group. Electrostic effects of overhead transmission lines, part I hazards and effects[J] . IEEE Trans on Power Apparatus and Systems, 1972, 91(2) : 422-426.
  • 9Anzivino L D, Gela G. HVDC transmission line reference book: EPRI TR-102764 [M]. Redlards, California: EPRI Press, 1993.
  • 10Hamza A H. Evaluation of magnetic induction inside humans at high voltage substatiuns[J]. Electric Power Systems Research, 2005, 74(2): 231-237.