期刊文献+

接入网电信级前置端子阀控式铅酸蓄电池的开发与应用 被引量:4

Development and application of the front terminal VRLA lead-acid telecom batteries for access network
下载PDF
导出
摘要 蓄电池对于接入网直流供电系统的质量和可靠性具有举足轻重的作用,接入网配套电池优选电信级狭长型前置端子蓄电池,以保障系统的安全可靠性。本文通过对接入网应用失效普通型UPS类12V电池的解剖分析,找到了接入网应用蓄电池的失效原因,并针对失效原因从设计角度上提出了改善措施。本文还就接入网配套蓄电池的选择与维护提出了自己的看法。 The storage battery is very important for the quality and reliability of DC power supply system in the access network. The front terminal narrow telecom battery is the excellent selection to guarantee the safety and reliability of the system. In this text, the reasons of the failures of batteries in the access network are found by the post-mortem analyzation of the common 12 V UPS batteries which had failed to use for access network application, and some improvements in designing are proposed. We also present our opinions on selection and maintenance of batteries for access network.
出处 《蓄电池》 北大核心 2009年第3期99-106,共8页 Chinese LABAT Man
关键词 接入网 阀控式铅酸蓄电池 前置端子 access network valve-regulated lead-acid battery front terminal